3. Installing the CPX-1000
Mount the
Splitter
Assembly
Step 1
Step 2
Step 3
Step 4
Connect Plant
Battery and
Frame Ground
3-16
After you have installed the CPX shelves, install the STS-1 Splitter
Assemblies if your CPX is configured for STS-1. .
Note
The Splitter Assembly is shipped with 75 ohm BNC
terminators in place to prevent signal degradation.
These caps should be left in place until an STS cable is
connected, and should be replaced if the cable is
removed.
If necessary, reverse the mounting flanges to fit your rack.
Place the Splitter Assembly into position above the CPX.
Using a slotted screwdriver, insert four 12-24
screws to each flange to fasten the Splitter Assembly to the rack.
Repeat these steps for each Splitter Assembly.
Power comes in to the CPX rear panel at the A and B plant battery
power strips. The A and B power legs each may be connected to
either of the power connection points on the back of the shelf.
Danger
The –48VDC plant battery presents a potentially fatal shock
hazard. Use extreme caution when connecting it to the CPX
and other equipment that requires plant battery for operation.
1000-A2-GN22-00
1
-inch pan head
×
2
February 2003