Chapter 3: Setting Reference
It is necessary to perform a set reference measurement at the beginning of a job, whenever
the test fiber is disconnected from the transmitter, and whenever a reference verification fails.
The setup varies depending on the number of jumpers reference is selected.
Following procedures are only for MMEF, MM and SM fiber.
For 1 jumper dual-ended,
1. Connect FC1 to the Local TX port and SC1 to the Remote RX port.
2. Connect FC2 to the Remote TX port and SC2 to Local RX port.
FC1
SC2
TX
RX
3. Press the SETUP button > Testing Configuration and select "One Jumper" from Dual-
Ended column. Select Single or Bi direction depending on requirement.
Press the TOOLS button > Set Reference and press the "ok" button to set reference.
4.
FC2
SC1
TX
RX
3