Connection Of Power Circuit; Wiring Instructions; Terminal Strip X1A - KEB COMBIVERT F5 Installation Manual

Digital servo controller
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Installation and Connection
3.3

Connection of Power Circuit

3.3.1 Wiring instructions

Core cross-section 1,5 mm²
Strip 7 mm
Optional use of wire-end ferrule
After arresting the cable by removing the
screwdriver absolutely check for a firm fit
Attach / remove terminal strip only at
tensionless state

3.3.2 Terminal Strip X1A

Terminal strip X1A / 230 V class
• 230 V AC / 1-phase (L1/N)
• 230 V AC / 3-phase (L1, L2, L3)
• DC-Supply 250...370 V DC (++, --)
Absolutely observe the connecting voltage of the KEB COMBIVERT. A 230V-unit will
be immediately destructed on a 400V-power supply.
Never exchange the mains and motor cables.
Some countries demand that the PE-terminal is directly connected to the terminal
box (not over the mounting plate).
Terminal strip X1A / 400 V class
• 400 V AC / 3-phase (L1, L2, L3)
• DC-Supply 420...747 V DC (++, --)