KEB COMBIVERT F5 Installation Manual page 30

Digital servo controller
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Annex B
Use of Modular Drive System 07F5A1A-3E2F:
For 480 V Models, F5-A, Modular Drive System, consisting of two drive units, Cat.
No. 07F5A1A-3E2F:
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms
Symmetrical Amperes, 480 Volts Maximum, when Protected by Class CC Fuses only,
rated max. 6A, 600V.
"The maximum total motor load for the two Drive Units
of the F5-A housing, Modular Drive System shall not exceed the specified motor load
of one individual drive unit 07F5A1A-3E2F"
"The Minimum wire size for the DC Bus Wring shall be at least 14 AWG. The minimum
wire size for the 400/480V input/output wiring shall be at least AWG 14"
Fuses Class CC with 600V / 6A is required for B.C.P.
GB - 30
Principle of DC coupling
AC supply 400/480V
L1
L2
L3
Fuses
CC
PE
PE
L1
L2
L3
X1A
07F5A1A-3E2F
X1B
U
V
W
M
DC coupling
PE
++ --
PE L1 L2 L3 ++ --
07F5A1A-3E2F
X1A
X1B
U
V
W
M

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents