Display of burner data

Useful information for service and maintenance staff.
No additional mechanical counters required.

3.25 Burner hours run stage 1 (tBR1)

Auxiliary value for ascertaining the amount of energy consumed.
Display
0...65535
The current number of hours run of burner stage 1 or of a BMU will automatically be
displayed on this line.

3.25.1 Counting the hours run

The hours run of burner stage 1 are counted using the signal received from output E1
(e.g. the fuel valve). The input signal voltage must be AC 230 V.
Each time 2 full operating hours are registered, the new value will be written to non-
volatile memory. Only full hours are displayed, and no minutes.
This means that if the display is checked again after a short period of time, it may still
show the previous reading, if the burner has not yet completed another 2 operating
hours.
When using a BMU, the value transmitted will be displayed via PPS.

3.25.2 Average burner running time

Together with the display of the number of burner starts ( line 37), it is possible to
ascertain the average burner running time.
This information makes it possible to determine if:
the plant is correctly sized
the burner has become dirty
Basic Documentation RVA63.242, RVA53.242
Description of end-user settings
Unit
Hours
63/218
CE1P2373E
26.03.2001