Installation and Set-up
Make a selection in 8-53 Start Select to define how Bit 06
Ramp stop/start gates with the corresponding function on
a digital input.
Bit 07, Reset
Bit 07 = '0': No reset. Bit 07 = '1': Resets a trip. Reset is
activated on the signal's leading edge, i.e. when changing
from logic '0' to logic '1'.
Bit 08, Jog
Bit 08 = '1': The output frequency is determined by
3-19 Jog Speed [RPM].
Bit 09, Selection of ramp 1/2
Bit 09 = "0": Ramp 1 is active (3-41 Ramp 1 Ramp Up Time
to 3-42 Ramp 1 Ramp Down Time). Bit 09 = "1": Ramp 2
(3-51 Ramp 2 Ramp Up Time to 3-52 Ramp 2 Ramp Down
Time) is active.
Bit 10, Data not valid/Data valid
Tell the frequency converter whether to use or ignore the
control word. Bit 10 = '0': The control word is ignored. Bit
10 = '1': The control word is used. This function is relevant
because the telegram always contains the control word,
regardless of the telegram type. Turn off the control word,
if it should not be used when updating or reading
parameters.
Bit 11, Relay 01
Bit 11 = "0": Relay not activated. Bit 11 = "1": Relay 01
activated provided that Control word bit 11 is selected in
5-40 Function Relay.
Bit 12, Relay 04
Bit 12 = "0": Relay 04 is not activated. Bit 12 = "1": Relay 04
is activated provided that Control word bit 12 is selected in
5-40 Function Relay.
Bit 13/14, Selection of set-up
Use bits 13 and 14 to select from the 4 menu set-ups
according to Table 8.35.
Set-up
Bit 14
1
0
2
0
3
1
4
1
Table 8.35 4 Menu Set-ups
The function is only possible when Multi Set-Ups is selected
in 0-10 Active Set-up.
Make a selection in 8-55 Set-up Select to define how Bit
13/14 gates with the corresponding function on the digital
inputs.
Bit 15 Reverse
Bit 15 = '0': No reversing. Bit 15 = '1': Reversing. In the
default setting, reversing is set to digital in 8-54 Reversing
Select. Bit 15 causes reversing only when Ser. communi-
cation, Logic or or Logic and is selected.
MG11BC02
Design Guide
8.11.2 Status Word According to FC Profile
Follower-master
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
no.:
Illustration 8.17 Status Word
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Table 8.36 Status Word Bits
Explanation of the Status Bits
Bit 00, Control not ready/ready
Bit 00 = '0': The frequency converter trips. Bit 00 = '1': The
Bit 13
frequency converter controls are ready but the power
0
component does not necessarily receive any power supply
1
(in case of external 24 V supply to controls).
0
Bit 01, Drive ready
1
Bit 01 = '1': The frequency converter is ready for operation
but the coasting command is active via the digital inputs
or via serial communication.
Bit 02, Coasting stop
Bit 02 = '0': The frequency converter releases the motor. Bit
02 = '1': The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03 = '0' : The frequency converter is not in fault mode.
Bit 03 = '1': The frequency converter trips. To re-establish
operation, enter [Reset].
Danfoss A/S © Rev. 06/2014 All rights reserved.
(STW) (8-10 Control Profile = FC
profile)
STW
Output freq.
Bit = 0
Bit = 1
Control not ready
Control ready
Drive not ready
Drive ready
Coasting
Enable
No error
Trip
No error
Error (no trip)
Reserved
-
No error
Triplock
No warning
Warning
Speed ≠ reference
Speed = reference
Local operation
Bus control
Out of frequency limit
Frequency limit OK
No operation
In operation
Drive OK
Stopped, auto start
Voltage OK
Voltage exceeded
Torque OK
Torque exceeded
Timer OK
Timer exceeded
8
8
145