Fuse Tables - Danfoss FC 102 Design Manual

1.1-90 kw
Hide thumbs Also See for FC 102:
Table of Contents

Advertisement

Electrical Installation

6.2.4 Fuse Tables

Enclosure
type
A2
A3
B3
B4
C3
6
6
C4
A4
A5
B1
B2
C1
C2
Table 6.19 200-240 V, Enclosure Types A, B and C
96
Power [kW]
Recommended
fuse size
1.1-2.2
gG-10 (1.1-1.5)
gG-16 (2.2)
3.0-3.7
gG-16 (3)
gG-20 (3.7)
5.5-11
gG-25 (5.5-7.5)
gG-32 (11)
15-18
gG-50 (15)
gG-63 (18)
22-30
gG-80 (22)
aR-125 (30)
37-45
aR-160 (37)
aR-200 (45)
1.1-2.2
gG-10 (1.1-1.5)
gG-16 (2.2)
0.25-3.7
gG-10 (0.25-1.5)
gG-16 (2.2-3)
gG-20 (3.7)
5.5-11
gG-25 (5.5)
gG-32 (7.5-11)
15
gG-50
18-30
gG-63 (18.5)
gG-80 (22)
gG-100 (30)
37-45
aR-160 (37)
aR-200 (45)
Danfoss A/S © Rev. 06/2014 All rights reserved.
Design Guide
Recommended
Max. fuse
gG-25
gG-32
gG-63
gG-125
gG-150 (22)
aR-160 (30)
aR-200 (37)
aR-250 (45)
gG-32
gG-32
gG-80
gG-100
gG-160 (18.5-22)
aR-160 (30)
aR-200 (37)
aR-250 (45)
Recommended circuit
Max trip level [A]
breaker
Moeller
PKZM0-25
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
25
25
50
100
150
250
25
25
63
100
160
250
MG11BC02

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FC 102 and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF