Danfoss FC 102 Design Manual page 165

1.1-90 kw
Hide thumbs Also See for FC 102:
Table of Contents

Advertisement

General Specifications and ...
Cable
Mains
length [m]
voltage [V]
5
400
50
400
150
400
Table 9.21 Frequency converter, P4K0, T4
Cable
Mains
length [m]
voltage [V]
5
400
50
400
150
400
Table 9.22 Frequency converter, P7K5, T4
Cable
Mains
length [m]
voltage [V]
15
400
100
400
150
400
Table 9.23 Frequency converter, P11K, T4
Cable
Mains
length [m]
voltage [V]
36
400
100
400
150
400
Table 9.24 Frequency converter, P15K, T4
Cable
Mains
length [m]
voltage [V]
36
400
100
400
150
400
Table 9.25 Frequency converter, P18K, T4
Cable
Mains
length [m]
voltage [V]
36
400
100
400
150
400
Table 9.26 Frequency converter, P22K, T4
Cable
Mains
length [m]
voltage [V]
15
400
100
400
150
400
Table 9.27 Frequency converter, P30K, T4
MG11BC02
Design Guide
Rise time
Vpeak
[μsec]
[kV]
0.172
0.890
0.310
0.370
1.190
Rise time
Vpeak
[μsec]
[kV]
0.04755
0.739
0.207
1.040
0.6742
1.030
Rise time
Vpeak
[μsec]
[kV]
0.408
0.718
0.364
1.050
0.400
0.980
Rise time
Vpeak
[μsec]
[kV]
0.422
1.060
0.464
0.900
0.896
1.000
Rise time
Vpeak
[μsec]
[kV]
0.344
1.040
1.000
1.190
1.400
1.040
Rise time
Vpeak
[μsec]
[kV]
0.232
0.950
0.410
0.980
0.430
0.970
Rise time
Vpeak
[μsec]
[kV]
0.271
1.000
0.440
1.000
0.520
0.990
Danfoss A/S © Rev. 06/2014 All rights reserved.
dU/dt
[kV/μsec]
4.156
2.564
1.770
dU/dt
[kV/μsec]
8.035
4.548
2.828
dU/dt
[kV/μsec]
1.402
2.376
2.000
dU/dt
[kV/μsec]
2.014
1.616
0.915
dU/dt
[kV/μsec]
2.442
0.950
0.596
dU/dt
[kV/μsec]
3.534
1.927
1.860
dU/dt
[kV/μsec]
3.100
1.818
1.510
163
9
9

Advertisement

Table of Contents
loading