Direction Of Motor Rotation; Motor Insulation - Danfoss FC 102 Design Manual

1.1-90 kw
Hide thumbs Also See for FC 102:
Table of Contents

Advertisement

Electrical Installation
c, d) The total motor cable length specified in section 4.5, General Specifications, is valid as long as the parallel cables are
kept short (less than 10 m each).
d, e) Consider voltage drop across the motor cables.
e) Be aware of the maximum motor cable length specified in Table 6.35.
e) Use LC filter for long parallel cables.
Enclo-
Power
Voltage
1 cable
sure
Size
[V]
[m]
Type
[kW]
A5
5
400
150
500
150
A2, A5
1.1-1.5
400
150
500
150
A2, A5
2.2-4
400
150
500
150
A3, A5
5.5-7.5
400
150
500
150
B1, B2,
11-90
400
150
B3, B4,
500
150
C1, C2,
C3, C4
Table 6.35 Max. Cable Length for Each Parallel Cable, Depending
on Quantity of Parallel Cables.
Problems may arise at start and at low RPM values, if
motor sizes are widely different because small motors'
relatively high ohmic resistance in the stator calls for a
higher voltage at start and at low RPM values.
The electronic thermal relay (ETR) of the frequency
converter cannot be used as motor protection for the
individual motor of systems with parallel-connected
motors. Provide further motor protection by e.g.
thermistors in each motor or individual thermal relays.
(Circuit breakers are not suitable as protection).

6.4.4 Direction of Motor Rotation

The default setting is clockwise rotation with the frequency
converter output connected as follows.
Terminal 96 connected to U-phase
Terminal 97 connected to V-phase
Terminal 98 connected to W-phase
The direction of motor rotation is changed by switching 2
motor phases.
Motor rotation check can be performed using 1-28 Motor
Rotation Check and following the steps shown in the
display.
MG11BC02
Design Guide
2
3
4
cables
cables
cables
[m]
[m]
[m]
45
8
6
7
4
3
45
20
8
45
5
4
45
20
11
45
20
6
45
20
11
45
20
11
75
50
37
75
50
37
Danfoss A/S © Rev. 06/2014 All rights reserved.
Motor
U
V
W
2
2
2
U
V
W
1
1
1
FC
96
97
98
Motor
U
V
W
2
2
2
U
V
W
1
1
1
FC
96
97
98
Illustration 6.42 Motor Rotation Check Steps

6.4.5 Motor Insulation

For motor cable lengths ≤ the maximum cable length
listed in chapter 9 General Specifications and Trouble-
shooting, the motor insulation ratings listed in Table 6.36
are recommended. If a motor has lower insulation rating, it
is recommended to use a dU/dt or sine-wave filter.
Nominal Mains Voltage [V]
≤ 420
U
N
420 V < U
≤ 500
N
500 V < U
≤ 600
N
600 V < U
≤ 690
N
Table 6.36 Motor Insulation
Motor Insulation [V]
Standard U
= 1300
LL
Reinforced U
= 1600
LL
Reinforced U
= 1800
LL
Reinforced U
= 2000
LL
107
6
6