Danfoss FC 102 Design Manual page 101

1.1-90 kw
Hide thumbs Also See for FC 102:
Table of Contents

Advertisement

Electrical Installation
UL Compliance
Fuses or circuit breakers are mandatory to comply with NEC 2009. Danfoss recommends using a selection of the following
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or 500 V,
or 600 V depending on the frequency converter voltage rating. With the proper fusing the frequency converter Short Circuit
Current Rating (SCCR) is 100,000 Arms.
Power
Bussmann
[kW]
1)
Type RK1
1.1
KTN-R-10
1.5
KTN-R-15
2.2
KTN-R-20
3.0
KTN-R-25
3.7
KTN-R-30
5.5-7.5
KTN-R-50
11
KTN-R-60
15
KTN-R-80
18.5-22
KTN-R-125
30
KTN-R-150
37
KTN-R-200
45
KTN-R-250
Table 6.23 200-240 V, Enclosure Types A, B and C
Power
SIBA
[kW]
Type RK1
1.1
5017906-010
1.5
5017906-016
2.2
5017906-020
3.0
5017906-025
3.7
5012406-032
5.5-7.5
5014006-050
11
5014006-063
15
5014006-080
18.5-22
2028220-125
30
2028220-150
37
2028220-200
45
2028220-250
Table 6.24 200-240 V, Enclosure Types A, B and C
MG11BC02
Design Guide
Recommended max. fuse
Bussmann
Bussmann
Type J
Type T
JKS-10
JJN-10
JKS-15
JJN-15
JKS-20
JJN-20
JKS-25
JJN-25
JKS-30
JJN-30
KS-50
JJN-50
JKS-60
JJN-60
JKS-80
JJN-80
JKS-125
JJN-125
JKS-150
JJN-150
JKS-200
JJN-200
JKS-250
JJN-250
Recommended max. fuse
Littel fuse
Type RK1
KLN-R-10
KLN-R-15
KLN-R-20
KLN-R-25
KLN-R-30
KLN-R-50
KLN-R-60
KLN-R-80
KLN-R-125
KLN-R-150
KLN-R-200
KLN-R-250
Danfoss A/S © Rev. 06/2014 All rights reserved.
Bussmann
Bussmann
Type CC
Type CC
FNQ-R-10
KTK-R-10
FNQ-R-15
KTK-R-15
FNQ-R-20
KTK-R-20
FNQ-R-25
KTK-R-25
FNQ-R-30
KTK-R-30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Ferraz-
Shawmut
Type CC
ATM-R-10
ATM-R-15
ATM-R-20
ATM-R-25
ATM-R-30
-
-
-
-
-
-
-
Bussmann
Type CC
LP-CC-10
LP-CC-15
LP-CC-20
LP-CC-25
LP-CC-30
6
-
-
-
-
-
-
-
Ferraz-
Shawmut
3)
Type RK1
A2K-10-R
A2K-15-R
A2K-20-R
A2K-25-R
A2K-30-R
A2K-50-R
A2K-60-R
A2K-80-R
A2K-125-R
A2K-150-R
A2K-200-R
A2K-250-R
99
6

Advertisement