Powtran PI9000 series User Manual page 181

Frequency inverter
Hide thumbs Also See for PI9000 series:
Table of Contents

Advertisement

initialization
1: restore the factory setting, not including motor parameters
After y0.00 is set to 1, most of the inverter function parameters are restored to the
factory default parameters, but motor parameters, frequency command decimal point
(F0.02), fault recording information, cumulative running time , cumulative power-on time
and cumulative power consumption will not be restored.
2: clear history
To clear the history of the inverter's fault recording information, cumulative running
time , cumulative power-on time and cumulative power consumption
3: restore default parameter values including motor parameters
4: backup current user parameters
Backup the parameters set by the current user. Backup all function parameters. It is
easy to restore the default settings when user incorrectly adjust parameters.
501, Restore user backup parameters
Restore previous backup user parameters.
10: Clear keyboard storage area
Empty keyboard storage area 1 and keyboard storage area 2
11: upload parameter to keyboard storage area 1
Upload the parameters of the inverter to keyboard storage area 1
Restore the factory
parameters,
including
motor
parameters
Clear history
Restore
default
parameter
values,
including
motor
parameters
Backup current user
parameters
Restore user backup
parameters
Clear
keyboard
3
storage area
upload parameter to
keyboard storage area
3
1
upload parameter to
keyboard storage area
3
2
download
parameters
from
keyboard storage 1
area to the storage
3
system
download
parameters
from
keyboard storage 2
area to the storage
3
system
3
175
Chapter 5 Function parameter
not
1
2
3
4
501
10
11
12
the
21
the
22
3
3
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents