Powtran PI9000 series User Manual page 119

Frequency inverter
Hide thumbs Also See for PI9000 series:
Table of Contents

Advertisement

arrival
(shutdown without
output)
Undervoltage status
19
output
Communication
20
setting
21
Reserve
22
Reserve
Zero speed running 2
23
(shutdown with output)
Accumulated power-
24
on time arrival
Frequency level
25
detection FDT2 output
Frequency 1 reaches
26
output value
Frequency 2 reaches
27
output value
Current 1 reaches
28
output value
Current 2 reaches
29
output value
Timer reaches output
30
value
31
AI1 input exceed limit
32
Load droping
33
Reverse running
34
Zero current status
Module temperature
35
arrival
Software current
36
overrun
Lower limit frequency
37
arrival(stop with output)
Chapter 5 Function parameter
frequency reaches the lower limit frequency
Outputs OFF signal when the inverter is in the
state of stop
Outputs ON signal when the inverter is in
the undervoltage condition
Please refer to communication protocol.
Reserve
Reserve
Outputs ON signal when the inverter
output frequency is 0. Outputs ON signal too
when the inverter is in the state of stop
Outputs ON signal when the inverter's
accumulated power-on time(F6.08) exceeds the
set time by F7.20.
Please refer to the instructions of function
code F7.26, F7.27
Please refer to the instructions of function
code F7.28, F7.29
Please refer to the instructions of function
code F7.30, F7.31
Please refer to the instructions of function
code F7.36., F7.37
Please refer to the instructions of function
code F7.38, F7.39
Outputs ON signal when timer(F7.42)is
active and after the inverter's current running
time reaches the set time.
Outputs ON signal when the analog input
AI1 value is greater than F7.51 (AI1 input
protection upper limit) or less than F7.50 (AI1
input protection limit)
Outputs ON signal when the inverter is in
the load drop status.
Outputs ON signal when the inverter is in
the reverse running status.
Please refer to the instructions of function
code F7.32, F7.33
Outputs ON signal when the inverter
module radiator temperature(F6.06)reaches the
set temperature(F7.40).
Please refer to the instructions of function
code F7.34, F7.35
Outputs ON signal when the operating
frequency reaches the lower limit frequency
Outputs ON signal too when the inverter is in
the sate of stop
113