Chapter 5 Function parameter
F7.06
Jump frequency range
When the set frequency is in the jump frequency range, the Actual operating frequency
will run at the jump frequency close from the set frequency . The inverter can avoid
mechanical resonance point of load by setting jump frequency.
PI9000 can set two jump frequency points, if the two jump frequencies are set to 0, the
jump frequency function will be canceled. For the principle schematic of jump frequency and
its range, please refer to the following figure.
Output
frequency
Jump
frequency 1
Jump frequency availability
F7.07
during ac/deceleration
process
The function code is used to set whether the jump frequency is active or not in the
process of acceleration and deceleration.
If it is set to active, when the operating frequency is in the jump frequency range, the
Actual operating frequency will skip the set jump frequency boundary. The below figure
below shows the jump frequency status in the process of acceleration and deceleration.
Schematic diagram of jump frequency availability in the process of acceleration and deceleration.
F7.08
Acceleration time 2
F7.09
Deceleration time 2
F7.10
Acceleration time 3
F7.11
Deceleration time 3
输出频率 Hz
Jump
Jump
Frequency
frequency 2
跳跃频率幅度
range
跳跃频率幅度
跳跃频率 1
跳跃频率示意图
Schematic diagram of jump frequency
Output
输出频率 Hz
Frequency
跳跃频率 2
Jump frequency 2
Jump
frequency 1
加减速过程中跳跃频率有效示意图
0.00Hz
F0.19(maximum
frequency)
跳跃频率幅度
Jump frequency range
跳跃频率幅度
Time
时间 t
Invalid
Valid
跳跃频率幅度
Jump frequency range
跳跃频率幅度
Jump frequency range
Jump frequency range
Time
0.0s to 6500.0s
0.0s to 6500.0s
0.0s to 6500.0s
0.0s to 6500.0s
132
to
0.00Hz
0
0
1
时间 t
-
-
-
-