4-10. Stick Connections

4-11. Electrical Service Guide

NOTE
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 1999 National Electrical Code (NEC)
1 Choose a circuit breaker with time-current curves comparable to a time delay fuse. Time delay fuses are UL class RK5.
2 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" ( 65 amp and
above).
Y Failure to follow these fuse and circuit breaker recommendations could create an electrical shock or fire hazard.
OM-2240 Page 20
2
3
1
Actual input voltage should not fall below 103 volts AC or rise above 506 volts AC.
If actual input voltage is outside this range, unit may not operate according to
specifications.
1
2
Normal Operating
Y Turn off power before mak-
1
Connect electrode holder to weld
output terminal labeled Electrode.
2
Connect work lead to weld output
terminal labeled Work.
3
If desired, connect remote control
to Remote 14 receptacle (see Sec-
tion 4-7).
Single-Phase,
Single-Phase,
100% Duty
60% Duty
Cycle
Cycle
115
230
28
20
35
30
10
12
57 (17)
79 (24)
10
12
ing connections.
Electrode Weld Output
Terminal
Work Weld Output Terminal
Remote 14 Receptacle
803 429-a
Three-Phase, 60% Duty
Cycle
230
400
460
12.3
7.6
6.0
20
10
10
14
14
14
102
308
407
(31)
(94)
(124)
14
14
14