Resetting The Module - Allen-Bradley 1769-SM1 User Manual

Compact i/o to dpi/scanport module
Table of Contents

Advertisement

To set the fault configuration parameters
If you set Parameter 09 - [Idle Action 1], 26 - [Idle Action 2], or 43 -
[Idle Action 3] to "Send Flt Cfg," the values in the following 1769-SM1
module parameters are sent to the drive after an idle action occurs. You
must set these parameters to values required by your application.
Parameter
CH1
CH2
10
27
11
28
12 - 19 29 - 36 46 - 53 Flt Cfg x1 In
Changes to these parameters take effect immediately. A reset is not required.

Resetting the Module

Changes to settings on some module parameters require that you reset
the 1769-SM1 module before the new settings take effect. You can reset
the module by cycling power to the module or by using Parameter 02 -
[Reset Module]:
ATTENTION: Risk of injury or equipment damage exists. If the
module is transmitting control I/O to the drive, the drive may fault when
!
you reset the module. Determine how your drive will respond before
resetting a connected module.
Set the Parameter 02 - [Reset Module] to Reset Module:
Figure 3.18 Reset Screen on an LCD HIM
Port 2 Device
1769-SM1
Parameter #: 02
Reset Module
1
Reset Module
When you enter 1 = Reset Module, the module will be immediately
reset. When you enter 2 = Set Defaults, the module will set all module
parameters to their factory-default settings. The value of this parameter
will be restored to 0 = Ready after the module is reset.
Name
CH3
44
Flt Cfg Logic A 16-bit value sent to the drive for Logic
Command.
45
Flt Cfg Ref A 32-bit value (0 – 4294967295) sent to the
drive as a Reference or Datalink.
or
Important: If the drive uses a 16-bit
Flt Cfg x2 In
Reference or 16-bit Datalinks, the most
significant word of the value should be set to
zero (0).
Configuring the Module
Description
Value
Description
0
Ready (Default)
1
Reset Module
2
Set Defaults
3-17