Feedback Signal Detection Time; Feedback Fault Treatment; Sleep Frequency; Wake-Up Frequency, Sleep Time - Delta VFD-VE User Manual

General field oriented vector control drives
Table of Contents

Advertisement

Chapter 4 Parameters
 Feedback Signal Detection Time
08-08
Control
VF
VFPG
mode
Settings
This parameter is only valid when the feedback signal is ACI.
This parameter defines the time during which the PID feedback must be abnormal
before a warning is given. It also can be modified according to the system feedback
signal time.
If this parameter is set to 0.0, the system would not detect any abnormality signal.

Feedback Fault Treatment

08-09
Control
VF
VFPG
mode
Settings
This parameter is only valid when the feedback signal is ACI.
AC motor drive acts when the feedback signals (analog PID feedback or PG (encoder)
feedback) are abnormal.
 Sleep Frequency
08-10
Control
VF
VFPG
mode
Settings
 Wake-up Frequency
08-11
Control
VF
VFPG
mode
Settings
 Sleep Time
08-12
Control
VF
VFPG
mode
Settings
These parameters determine sleep functions of the AC drive. If the command frequency
falls below the sleep frequency, for the specified time in Pr. 08-12, then the drive will
4-138
SVC
FOCPG
0.0 to 3600.0 sec
SVC
FOCPG
0
Warn and keep operating
1
Warn and RAMP to stop
2
Warn and COAST to stop
3
Warn and keep at last frequency
SVC
FOCPG
0.00 to 600.00Hz
SVC
FOCPG
0.00 to 600.00Hz
SVC
FOCPG
0.0 to 6000.0sec
Unit: 0.1
Factory Setting: 0.0
Factory Setting: 0
Unit: 0.01
Factory Setting: 0.00
Unit: 0.01
Factory Setting: 0.00
Unit: 0.1
Factory Setting: 0.0