 External Operation Control Selection after Reset
02-34
Control
VF
VFPG
mode
Settings
After clearing fault once a fault is detected and the external terminal for RUN keeps ON,
the drive can run after pressing RESET key.
 Zero-speed Level of Motor
02-43
Control
VFPG
FOCPG TQCPG
mode
Settings
This parameter should be used with the multi-function output terminals (set to 43).
This parameter is used to set the level of motor zero-speed. When the actual speed is
lower than this setting, the corresponding multi-function output terminal 43 will be ON
as shown as follows.
a ctua l mo tor
sp ee d
MO =d 43
SVC
FOCPG TQCPG
0: Disable
1: Drive runs if run command exists after reset
0~65535rpm
0 2- 43
Chapter 4 Parameters
Factory setting: 0
Factory setting: 0
Ti me
Unit:1
Unit: 1
4-93