CONNECTION TO MATCHING EXTERNAL BATTERY CABINET

Please follow below instructions for external battery cabinet connections:
Ensure that the UPS is disconnected from mains and loads while connecting the
External Battery Cabinet. Use the battery cable that comes with the External Battery
Cabinet to connect the External Battery Cabinet to the UPS. Connect a second
battery cabinet to the first one with the cable provided if more than one is to be
installed.
This UPS may be provided with maximum two extension battery cabinets.
T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001

Figure 9 Connecting External Battery Cabinet