4. Carefully inspect the flared pipe end.
• Compare the geometry with Figure 5-1 and the dimensions detailed in Figure 5-2 and Table 5-1.
Figure 5-2 Flared-connection dimensions
Pipe
Vapor (in. O.D.)
Liquid (in. O.D.)
1/2
5/8
5.1.2
Tightening Flare Nuts
NOTE
Do not use polyolyester (POE) or any other type of mineral oil as a thread
lubricant. These lubricants are not compatible with PVE oil used in this system
and create oil sludge leading to equipment damage and system malfunction.
1. When connecting the flare nuts, coat the flare (inside and outside) with polyvinyl ether (PVE)
refrigeration oil only.
2. Initially, hand tighten the flare nuts using 3 or 4 turns.
3. Finishing tightening the flare nuts using both a torque wrench and a backup wrench as shown in
Figure 5-3.
Pipe size (in. O.D.)
Figure 5-3 Tightening the flare nuts
Table 5-1
Flared-connection dimensions
Vapor (in.)
1/4
1/8
3/8
1/8
Table 5-2
Tightening torque for flare nuts
Tightening torque (ft-lbs)
∅
1/4
∅
3/8
∅
1/2
∅
5/8
90°
2
A
R=0.4~0.8
"A"
Liquid (in.)
1/16
1/16
Width of flare (A [in.])
13.9 – 18
24.5 – 30.3
39.7 – 47.7
45.5 – 59.2
Union
37
Thickness
Vapor (in.)
Liquid (in.)
1/8
1/8
1/16
1/8
1/8
1/8
1/8
1/16
®
Liebert
SRC™ User Manual
Piping