Contents Chapter 1 Overview ................................1 1.1 Product Introduction .............................. 1 1.2 Nomenclature of the CRV+ Air Cooled AC Unit ....................1 1.3 Appearance ................................2 1.4 Main Components Of Indoor Unit.......................... 2 1.5 Refrigerant Requirement ............................3 Chapter 2 Instruction For Pre-installation ..........................4 2.1 Equipment Room Consideration ...........................
Page 4
4.2 Connecting Cables Of Indoor Unit ........................23 4.2.1 Electrical Port Location Of Indoor Unit ..................... 23 4.2.2 Connecting Power Cable Of Indoor Unit ....................24 4.2.3 Connecting Control Cable........................25 4.2.4 Connecting Solenoid Valve Of Pipe Extension Kit (Option For Site Installation) ........26 4.3 Checklist For Completed Installation ........................
Page 7
Forward Liebert.CRV+ series air cooled air conditioner is precision air conditioner used in data center, which is developed based on the Global R&D Platform of Emerson Network Power Co., Ltd.(“Emerson” for short hereafter). This manual focuses on the using instructions, including instructions for installation preparations, mechanical installation, electrical installation, controller operation, system operation and maintenance, and troubleshooting, etc.
Chapter 1 Overview Chapter 1 Overview The Liebert.CRV+ series air cooled precision air conditioner (CRV+ air cooled AC unit for short) is a professional device, applicable to occasions inaccessible to general public. This chapter introduces CRV+ air cooled AC unit appearance, model description, refrigerant requirement, main components of indoor unit and requirements on operation and storage environment.
Sight glass is used to observe the refrigerant state and the moisture level content of the system. If the moisture content level exceeds the standard level, the color of the sight glass indicator will change. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Poor quality or counterfeit refrigerant will damage the system severely. Please use the refrigerant approved by Emerson. For the system abnormity or damage caused by using poor quality refrigerant, the warranty will be invalid. Please do not use poor quality refrigerant. For any result caused by using poor quality refrigerant, the warranty will be invalid.
In normal condition, leave more than 600mm of clearance at the front and the rear of the air condition unit, as shown in Figure 2-1 and Table 2-1. 1945 Figure 2-1 Space clearance for maintenance (unit: mm) Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Top cover 2. First remove the winding stretch film, and then 1. Remove remove the the top honeycomb cover . cardboard. Honeycomb Honeycomb cardboard cardboard Figure 2-4 Unpacking the outer package Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
If any parts are found missing or damaged, please report to the carrier immediately. If any covert defects are found, please report to the carrier and the local office of the distributor. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
The manufacturer’s engineering dimension drawings can be served as a reference. 3.2 System Arrangement 3.2.1 General Arrangement The general arrangement of the CRV+ air cooled AC unit is shown in Figure 3-1. Figure 3-1 Overall system arrangement Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
: Factory piping. : Field piping (by technical personnel). *: These components are not supplied by Emerson, but are recommended for normal circuit operation and maintenance. +: These components are required to add in field when the pipe equivalent length exceeds 30m.
A:Drainage hole of pump B: Liquid pipe hole C: Discharge pipe hole D: Cable entry hole E:Inlet hole of humidifier F:Drainage hole of water tray Figure 3-5 Locations of base plate pipe outlet Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Page 19
Front air outlet locations & dimensons The front air outlet locations & dimensions are shown in Figure 3-7. 1895 1895 CR035 CR025 Figure 3-7 Front air outlet locations & dimensions (unit: mm) Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
3-9. Install bolts in the four bottom holes to fix the cabinet onto the floor bracket of the machine room, and install bolts in the four top holes to connect the cabinet with the top bracket of the machine room. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
2. Use the M5 countersunk head screws to fix the cabinet connector (L shape) in the installation holes of the cabinet frame (side of the hinge) and the rack frame adjacent to the cabinet, as shown in Figure 3-11. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Use Teflon belt between the flexible pipes and connector to avoid water leakage , Note Because the electrode humidifier contains flowing hot water, the plastic pipe must be resistant to heat higher than 90°C. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Some product may contain components involved in local laws and regulations. Top water inlet Water inlet Water inlet copper pipe hole soft pipe Figure 3-15 Connection of bottom water inlet pipe of electrode humidifier Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
2. D: discharge line, L: liquid line. 3. Consult Emerson if the pipe length exceeds 50m. 4. If the outdoor environment temperature is lower than -20°C, a low temperature kit is needed, please consult Emerson Network Power Co., Ltd. 进水孔...
If the one-way equivalent length exceeds 30m, or if the vertical distance between indoor unit and condenser exceeds the values in Table3-5, consult Emerson before installation to confirm whether extension kit is needed. The recommended pipe sizes are ‘equivalent lengths’ (see Table 3-6 for equivalent lengths of partial components), with the resistance caused by bends taken into account.
If the connection pipe between the indoor unit and the outdoor unit is longer than 10m, refill the refrigerant to the system to ensure normal system operation according to Table 3-10. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Page 28
Poor quality refrigeration oil should not be used for it can damage system; Select the right type of refrigeration oil., and incorrect model should not be used; For any result caused by wrongly adding of refrigeration oil, the warranty will be invalid. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
For smooth installation on site and connection of the rack on the top of the machine room, there are some holes reserved on the top of the cabinet. After the cabinet is installed on the site, rubber plugs and blots are needed to seal Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
After installation, foreign materials in and around the equipment are removed (such as shipping materials, construction materials, tools, and so on) You can start electrical installation after confirming the preceding items. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
4.2.1 Electrical Port Location Of Indoor Unit For the Liebert.CRV+ series unit, open the back door of indoor unit, you can see the specific layout and locations of low voltage components, as shown in Figure 4-1. For the detailed layout information of low voltage components, refer to the label pasted on the cabinet for distinguishing.
Table 4-1 Full-load current (unit: A) Standard Standard model Standard model Standard model with electric Model model with electric heater with humidifier heater and humidifier CR025HA1380S02E10000PV000 24.9 24.9 CR025RA138SS12E10000PV000 CR035HA1380S02E10000PV000 31.6 46.6 42.3 46.6 CR035RA138SS12E10000PV000 46.6 Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
The standard location of the sensor is 1.5m height. Therefore, the sensors should be placed on positions shown in Figure 4-4, or the devices cannot operate normally. Sensor 传感器 传感器 1.5m 1.5m 1.5m 1.5m 1.5m Figure 4-4 Layout figure of rack sensors Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
The circuit breakers or fuses have proper ratings for equipment installed (refer to the current listed in Table 4-1 for selecting apporopriate circuit breakers or fuses) Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Page 35
All wiring and connector connections are tight. The fixing bolts are tight After confirming the preceding points, you can start the commissioning operation. Do not power on the unit until Emerson authorized technical has checked and confirmed the unit. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
5.1 Location Of MCBs The MCB locations of Liebert.CRV+ series unit are shown in Figure 5-1. For the MCB distribution in different unit electrical control box, please refer to the actual label on the cabinet for distinguishing.
(compressor output 72%, fan output 60%) and perform dynamic charging. After the compressor starts, if the refrigerant cannot be charging, you can place the refrigerant cylinder upside down. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Check item Result Check that all output functions are automatic Check that the temperature & humidity settings and control precisions are set reasonable Make sure all the other functions are set reasonable Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
LCD screen, it displays unit output status (fan, cooling, heating, dehumidifying and humidifying), unit mode (single, teamwork), and unit operation status (off, running, standby, locked), as shown in Figure 6-2. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
1. Press the Up or Down button to move the cursor on the Alarm Menu in the Main Menu screen. 2. Press the Enter button to enter the Alarm Menu. 3. Press the Up or Down button to move the cursor on Alarm Set in the Alarm Menu screen. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Fan rotating speed. Displaying the percentage of actual fan rotating speed Compressor capacity. Displaying the percentage of actual compressor capacity Heating state. Displaying 100% in heating mode, otherwise, displaying 0% Humidifying state. Displaying 100% in humidifying mode, otherwise, displaying 0% Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
For detailed setting procedures, refer to 6.4.2 Operation Example. <Alarm Menu> <Temp&Hum Set> <System State> <System Set> Figure 6-7 Main Menu The menu items in the Main Menu screen are described in Table 6-4. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Figure 6-10. XX is the serial number of the historical alarm record and YY is the total number of the historical alarm records. Figure 6-10 Alarm History Menu Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Page 44
Select Alarm Stpt on the Alarm Set screen to enter the screen shown in Figure 6-13. Press the Up or Down button to scroll through the menus. Figure 6-13 Alarm setpoint Menu Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Page 45
CP Driver Alarm Select CP Driver Alarm on the Alarm Set screen to enter the screen shown in Figure 6-16. Press the Up or Down button to scroll through the menus. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Figure 6-18 Alarm Process Menu 6.6.3 Temp&Hum Set Select Temp&Hum Set on Main Menu screen to enter the screen shown in Figure 6-19. The temperature & humidity settings will not be cleared upon system power-off. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
The Run State menu displays important operating parameters of devices, including ambient temperature & humidity, and the running states of compressor, fan and EEV, as shown in Figure 6-21. Figure 6-21 Run State Menu Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Page 48
Select On/Off Record on System State screen to enter the screen shown in Figure 6-25. You can view the start and stop records of important components through this menu. the On/Off Record will not be cleared upon power-off. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Up or Down button to select YES or NO, and press the Enter button to confirm it. If YES is selected, all system settings will be restored to factory values, however, any running time records or historical alarm records will not be cleared. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Page 50
Comp Set The Comp Set screen is shown in Figure 6-30. Figure 6-30 Comp Set Menu EEV Set The EEV Set screen is shown in Figure 6-31. Figure 6-31 EEV Set Menu Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
<Enab 1st Run> Figure 6-34 Help Menu Date&Time The Date&Time screen displays the current time and date of the system in the format of Year/Month/Date and Hour/Minute/Second, as shown in Figure 6-35. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Figure 6-37 Version Info Menu 6.6.7 Display Set Select Display Set on Main Menu screen to enter the Display Set screen, as shown in Figure 6-38. Figure 6-38 Display Set Menu Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Check for clogging or damage Air Filter Check the filter clogging switch Clean the filter Fan blades are not distorted The bearings are not worn out Check and fasten the circuit connections Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
2. Check that there is no signs of aging on the control interface board, control board, temperarure and humidity sensor board and fuse board. 3. Clean the electric control components and control board off dust and dirt with brush and electronic dust removing agent. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
The fan operating time is 2160 hours by default (the operating time is settable according to local operating environment), and the filter maintenance alarm is triggered. You should check and Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
THS. If a call for humidification is registered, the micro-processing controller will send a humidification command to the humidification control board, and provide 24V power to it. Then the humidification Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
4. Remove the connection cable of the humidification electrode and high water level probe from the canister. Note Canister and steam hose may be very hot! Allow time for the humidifier to cool before replacement. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
See Table 7-4 for details. Table 7-4 Discharge pressure System design kPa (PSIG) High pressure switch action point 3700 Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
When electric fault occurs and the compressor motor is entirely burned, the system must be cleaned to remove the acid material from the system and to avoid such faults in the future. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
When the compressor is entirely burned, you need to replace the filter drier together with the compressor. In addition, check the expansion valve. If the valve is faulty, replace it too. Before the replacement, you must clean the system. If you are unsure about the cleaning method, please consult with Emerson service personnel. 7.10 Drainage System Maintenance Guidance Inspect water tray periodically for normal operation of the drainage pipe.
2. Check L1, L2 and L3 voltages are normal when the contactor is Contactor closes, but heating is ineffective energized. Electric heater burned Turn off the power the physically check the condition of the heater. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Page 62
Check that the fans of the evaporator and condenser are normal Compressor over-temperature Too high suction overheat Regulate the electronic expansion valve or add proper amount degree of refrigerant Note:Judging the above symptoms is based on refrigerating command Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Appendix 1 Circuit Diagram Appendix 1 Circuit Diagram Figure 1 CR035 circuit diagram Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Page 64
Factory supplied 24 volt wiring BL- Blue R-Red Device own line BR-Brown YE-Yellow Inline quick disconnect WH-White GR-Grey Terminal block connector Y/GN-Yellow green Naked crimping connector Figure 2 CR025 circuit diagram Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Appendix 2 Menu Structure Of Micro-Processing Controller Appendix 2 Menu Structure Of Micro-Processing Controller Help Menu Remote Alm Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
Ret Hum Sensor Alarm Hi HS Temp Hi Exh Lock Air Temp Sensor Alarm Comp OC Lo Exh Lock Sup Temp Sensor Alarm Comp PL Power Lost Rem Temp Sensor Alarm BV Abnor Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
×: Means the content of the hazardous substances in at least one of the average quality materials of the part is outside the limits specified in SJ/T11363-2006 Emerson Network Power Co., Ltd. has been committed to the design and manufacturing of environment-friendly products. It will reduce and eventually eliminate the harzardous substances in the products through unremitting efforts in research. However,...
___ 5. Check the electronic expansion valve Heating system ___ 1. Check the re-heater operation ___ 2. Check the erosion situation of the components Signature: _________________________________________________________ Note: copy this table for filing. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...
___ 5. Check the voltage regulating function of the rotation speed controller ___ 4. Check the contactor action ___ 6. The temperature switch is set at the required position Signature _________________________________________________________ Note: copy this table for filing. Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual...