Figure 6-11 Src18 Outdoor-Unit Terminal-Block Connections - Emerson Liebert SRC18 User Manual

Mini-split cooling system
Table of Contents

Advertisement

5. Using a screwdriver, refer to Figure 6-11 or Figure 6-12, and connect the wires as follows:
• Securely attach each wire to the terminal block.
• Bundle cabling using a cable restrainer.
• Pay attention to the location/connection of the green/yellow grounding cable. In some models, the
connection is located on the side of the actual terminal block.
• Maintain a minimum of 0.2-in. of wire length from the terminal block to cable bundle.

Figure 6-11 SRC18 outdoor-unit terminal-block connections

180HSV4
Outdoor Unit
Terminal Block
Over 0.2"
Power Cord
Conduit Panel Cover
1(L1) 2(L2)
1(L1) 2(L2 ) 3
Conduit Panel
Connection/Communication
Cable (Leading to Indoor Unit)
79
Electrical Connections
®
Liebert
SRC™ User Manual