7.6 Setting the Ceiling Height
Refer to Table 7-1 for the specific function-setting values.
1. On the thermostat, press
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters "user" settings mode.
2. Press
repeatedly to select the function code.
3. Press
, to select the Value, then use
descriptions of the ceiling-height settings.
01
02
03
04
4. Press
.
The setting is saved.
5. Press
to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing
7.7 Setting Fahrenheit/Celsius
Refer to Table 7-1 for the specific function-setting values.
1. On the thermostat, press
The function code blinks in the lower-middle of the display.
NOTE
A press less than 3 seconds enters "user" settings mode.
2. Press
to select the function code.
3. Press
, to select Value, then use
4. Press
.
The setting is saved.
5. Press
to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing
for at least 3 seconds.
Table 7-3
Ceiling-height setting options
Value
Low
Decrease indoor air-flow rate 1 step from standard level.
Medium
Set indoor air-flow rate as standard level.
High
Increase indoor air-flow rate 1 step from standard level.
Very high
Increase indoor air-flow rate 2 steps from standard level.
, your settings are not saved.
for at least 3 seconds.
, your settings are not saved.
Installation Set-up and System Start-up
to select the setting. Refer to Table 7-3 for
Function
to select the setting.
89
®
Liebert
SRC™ User Manual