3.2.8 Copy mode

By using the operation panel (FR-DU04), the parameter values can be copied to other FR-F500 series
inverters.
1) Operation procedure
After reading the parameter values from the copy source inverter, connect the operation panel to the copy
destination inverter, and write the parameter values.
After writing the parameters to the inverter of copy destination, always reset the inverter, e.g. switch power
off once, before starting operation.
#Parameter setting mode
FR-DU04
CONTROL PANEL
Hz
A
V
MON
EXT
PU
REV
FWD
FR-DU04
CONTROL PANEL
Hz
A
V
MON
EXT
PU
REV
FWD
Note: 1. While the copy function is being activated, the monitor display flickers. The display returns to the
lit-up state on completion of the copy function.
2. If a read error occurs during parameter read, "read error (E.rE1)" is displayed.
3. If a write error occurs during parameter write, "write error (E.rE2)" is displayed.
4. If a data discrepancy occurs during parameter verify, the corresponding parameter number and
"verify error (E.rE3)" are displayed alternately. If the direct frequency setting or jog frequency
setting is discrepant, "verify error (E.rE3)" flickers. To ignore this display and continue verify,
press the
SET
5. When the copy destination inverter is not the FR-F500 series, "model error (E.rE4)" is displayed.
Reference: It is recommended to read the parameter values after completion of parameter setting.
By writing the parameter values from the operation panel fitted to a new inverter after inverter
replacement, parameter setup can be completed.
FR-DU04
CONTROL PANEL
MON
EXT
PU
REV
FWD
FR-DU04
CONTROL PANEL
SET
MON
EXT
PU
REV
FWD
Press for
(Note 1)
SET
1.5 s.
FR-DU04
CONTROL PANEL
MON
EXT
PU
REV
FWD
#Parameter read
Connect to copy destination inverter.
key.
Hz
A
V
FR-DU04
CONTROL PANEL
Hz
A
V
MON
EXT
REV
Press for
(Note 1)
SET
1.5 s.
FR-DU04
CONTROL PANEL
Hz
A
V
MON
EXT
REV
#Parameter write
After writing the parameters,
always reset the inverter before
operation.
53
OPERATION/CONTROL
FR-DU04
Hz
A
V
PU
MON
EXT
FWD
REV
Press for
SET
1.5 s.
FR-DU04
Hz
A
V
PU
MON
EXT
FWD
REV
#Parameter verify
CONTROL PANEL
Hz
A
V
PU
FWD
(Note 1)
CONTROL PANEL
Hz
A
V
PU
FWD

Advertisement

Table of Contents
loading

Table of Contents