Mitsubishi Electric FR-F500 Series Instruction Manual page 79

Transistorized inverter
Hide thumbs Also See for FR-F500 Series:
Table of Contents

Advertisement

Func-
Parameter
tion
Number
$ 240
Soft-PWM setting
$ 244
Cooling fan operation selection
251
Output phase failure protection selection
252
Override bias
253
Override gain
500
Auxiliary motor operation selection
501
Motor switch-over selection
502
MC switching interlock time
503
Start waiting time
Auxiliary motor connection-time
504
deceleration time
Auxiliary motor disconnection-time
505
acceleration time
506
Output stop detection time
507
Output stop detection level
508
Output stop cancel process value level
509
Auxiliary motor 1 starting frequency
510
Auxiliary motor 2 starting frequency
511
Auxiliary motor 3 starting frequency
512
Auxiliary motor 1 stopping frequency
513
Auxiliary motor 2 stopping frequency
514
Auxiliary motor 3 stopping frequency
515
Auxiliary motor start delay time
516
Auxiliary motor stop delay time
$ 900
FM terminal calibration
$ 901
AM terminal calibration
$ 902
Frequency setting voltage bias
$ 903
Frequency setting voltage gain
$ 904
Frequency setting current bias
$ 905
Frequency setting current gain
$ 990
PU buzzer control
991
Parameter for option (FR-PU04)
Note: 1. The setting depends on the inverter capacity.
2. Can be accessed when Pr. 29 = 3.
3. The half-tone screened parameters allow their settings to be changed during operation if 0
(factory setting) has been set in Pr. 77. (Note that the Pr. 72 and Pr. 240 settings cannot be
changed during external operation.)
The parameters which can be changed whilst the inverter is running will also depend upon the
setting of Pr. 160 "user group read selection".
4. The setting depends on the inverter capacity: (0.75K)/(1.5K to 3.7K)/(5.5K, 7.5K)/(11K or more).
5. Setting may be made for the NA and EC versions only.
Name
Setting Range
0 to 3600s, 9999
0 to 3600s, 9999
0 to 10V
0 to 10V
0 to 20mA
0 to 20mA
66
Minimum
Setting
Increments
0, 1
1
0, 1
1
0, 1
1
0 to 200%
0.1%
0 to 200%
0.1%
0 to 3
1
0 to 2
1
0 to 100s
0.1s
0 to 100s
0.1s
0 to 3600s
0.1s/0.01s
0.1s/0.01s
0.1s/0.01s
0 to 120Hz
0.01Hz
0 to 100%
0.1%
0 to 120Hz
0.01Hz
0 to 120Hz
0.01Hz
0 to 120Hz
0.01Hz
0 to 120Hz
0.01Hz
0 to 120Hz
0.01Hz
0 to 120Hz
0.01Hz
0 to 3600s
0.1s
0 to 3600s
0.1s




0 to 60Hz
0.01Hz
1 to
0.01Hz
120Hz
0 to 60Hz
0.01Hz
1 to
0.01Hz
120Hz
0, 1
1
PARAMETERS
Factory
Cust-
Refer
Setting
omer
To
〈 〈 〈 〈 EC
Set-
Page:
Version〉 〉 〉 〉
ting
1
100
0
145
1
145
50%
146
150%
146
0
147
0
147
1s
147
1s
147
1s
147
1s
147
9999
147
0Hz
147
100%
147
60Hz
147
〈50Hz〉
60Hz
147
〈50Hz〉
60Hz
147
〈50Hz〉
0Hz
147
0Hz
147
0Hz
147
5s
147
5s
147

158

158
0V
0Hz
160
60Hz
5V
160
〈50Hz〉
4
0Hz
160
mA
20
60Hz
160
〈50Hz〉
mA
1
165