Mitsubishi Electric FR-F500 Series Instruction Manual page 143

Transistorized inverter
Hide thumbs Also See for FR-F500 Series:
Table of Contents

Advertisement

( 1 ) Wiring example
Sink logic, Pr. 185 = 7, Pr. 186 = 6, Pr. 192 = 17, Pr. 193 = 18, Pr. 194 = 19
NFB
MC1
Inverter start
(forward rotation)
Inverter-commercial
power supply switch-over
Operation interlock
External thermal relay
Reset
Frequency setting signal
Note: !This switch-over function is used in the external operation
mode. Always connect terminals R1, S1 (L
different power supply (power supply different from the one
for MC1) to ensure proper operation.
!MC2 and MC3 must be mechanically interlocked.
*1. Note the sequence output terminal capacities. The terminals used
depend on the Pr. 190 to Pr. 194 settings.
Output Terminal Capacity
Inverter's open collector outputs
(IPF, OL, FU)
FR-A5AR (option output)
*2. When connecting an AC power supply, connect the FR-A5AR option
and use the contact output.
When connecting a DC power supply, install the following protective
diode.
*3. The terminals used depend on the Pr. 180 to Pr. 186 settings.
MC2
×
External
Inverter
thermal relay
MC3
R 〈L
U
1
S 〈L
V
IM
2
T 〈L
W
3
R1 〈L
11
S1 〈L
21
Signal set in Pr. 190 to Pr. 195
SU
*1
MC
IPF
STF
1
MC3
CS
*1
MC
OL
MRS
2
MC2
*1
MC
FU
*3
3
OH
SE
RES
SD
10
2
IPF
5
RA
OL
FU
SE
, L
) to a
11
21
Permissible Output Terminal Load
24VDC 0.1A
230VAC 0.3A
30VDC 0.3A
130
PARAMETERS
*2
DC24V
DC
24V

Advertisement