Mitsubishi Electric FR-F500 Series Instruction Manual page 176

Transistorized inverter
Hide thumbs Also See for FR-F500 Series:
Table of Contents

Advertisement

(3) Read Pr. 903 and show the current setting of the gain frequency.
(Pr. 902, Pr. 904 and Pr. 905 can also be adjusted similarly.)
#Parameter setting mode
Using the
FR-DU04
MON
Most significant
digit flickers.
Current setting of gain frequency
FR-DU04
MON
(4) Set a gain frequency in Pr. 903 and show the analog voltage value across terminals 2-5 in %. (when
setting the frequency to 80Hz)
Current setting of
gain frequency
FR-DU04
MON
key, choose the "parameter setting mode" as in (2)-1).
MODE
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
SET
Middle digit
flickers.
×9
times
SET
0 to 9
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
#Changing the gain
frequency
FR-DU04
CONTROL PANEL
Hz
A
V
EXT
PU
MON
EXT
REV
FWD
REV
Press
change the set frequency.
#
Analog voltage value (%)
across terminals 2-5
FR-DU04
MON
EXT
In any of the methods in (5) to (7) on the following page,
continue the setting until the analog voltage value
flickers. If you end the setting here, the gain frequency
change will not be reflected.
163
Least significant
digit flickers.
SET
0 to 9
CONTROL PANEL
Hz
A
V
PU
FWD
to
Press for 1.5 s
SET
CONTROL PANEL
Hz
A
V
PU
REV
FWD
PARAMETERS
×3
times
SET
4

Advertisement

Table of Contents
loading

Table of Contents