# For the data codes of the parameters, refer to the data code list in the appendices.
REMARKS
For computer link operation, set the value "8888" as 65520 (HFFF0) and the value "9999" as 65535
(HFFFF).
Parameter
Number
117
118
119
120
121
122*
0 <9999>
123
124
* To make communication, set any value other than 0 in Pr. 122 "communication check time interval".
<Setting>
To make communication between the personal computer and inverter, the communication specifications
must be set to the inverter initially. If initial setting is not made or there is a setting fault, data transfer cannot
be made.
Note: After making the initial setting of the parameters, always reset the inverter. After you have changed the
communication-related parameters, communication cannot be made until the inverter is reset.
Parameter
Description
Number
Communication
117
station number
Communication
118
speed
Stop bit length/data
119
length
Parity check
120
presence/
absence
Number of
121
communication
retries
Communication
122
check time interval
123
Waiting time setting
CR • LF presence/
124
absence selection
Factory
Setting Range
Setting
0
0 to 31
192
48, 96, 192
Data length 8
1
Data length 7
2
0, 1, 2
1
0 to 10, 9999
0, 0.1 to 999.8 s, 9999
9999
0 to 150ms, 9999
1
0, 1, 2
Setting
0 to 31
48
96
192
0
8 bits
1
10
7 bits
11
0
1
2
0 to 10
9999
(65535)
0
0.1 to 999.8
9999
0 to 150ms
9999
0
1
2
0, 1
10, 11
Communication station number specified for communication from the PU
connector.
Set the inverter communication station numbers when two or more inverters
are connected to one personal computer.
4800 bps
9600 bps
19200 bps
Stop bit length 1 bit
Stop bit length 2 bits
Stop bit length 1 bit
Stop bit length 2 bits
Absent
Odd parity present
Even parity present
Set the permissible number of retries at occurrence of data receive error. If
the number of consecutive errors exceeds the permissible value, the inverter
will come to an alarm stop.
If a communication error occurs, the inverter will not come to an alarm stop.
At this time, the inverter can be coasted to a stop by MRS or RES input.
During a communication error (H0 to H5), the minor fault signal (LF) is
switched on. Allocate the used terminal with any of Pr. 190 to Pr. 195 (output
terminal function selection).
No communication
Set the communication check time [s] interval.
If a no-communication state persists for longer than the permissible time, the
inverter will come to an alarm stop.
Set the waiting time between data transmission to the inverter and response.
Set with communication data.
Without CR • LF
With CR • Without LF
With CR • LF
112
PARAMETERS
Description