Mitsubishi Electric FR-F500 Series Instruction Manual page 146

Transistorized inverter
Hide thumbs Also See for FR-F500 Series:
Table of Contents

Advertisement

( 3 ) Operation procedure
1) Operation procedure for running
Operation pattern
Switch power on.
Set parameters.
Start, inverter operation
Constant-speed operation,
commercial power supply
operation
Deceleration (stop),
inverter operation
2) Signal on-off after parameter setting
MRS
OFF
Power on
(OFF)
At start
OFF→ON
(Inverter)
Constant speed
(Commercial
ON
power supply)
Switched to
inverter
operation for
ON
deceleration
(Inverter)
Stop
ON
! Pr. 135 = "1" (inverter's open collector output terminals)
! Pr. 136 = "2.0 s"
! Pr. 137 = "1.0 s" (Set the value equal to or longer than the time
from when MC3 switches on actually until the inverter and
motor are connected. If it is shorter, restart may not function properly.)
! Pr. 57 = "0.5 s"
! Pr. 58 = "0.5 s" (Always set this parameter when commercial power
supply operation is switched to inverter operation.)
CS
STF
OFF
OFF
OFF→ON
(OFF)
(OFF)
(OFF→ON)
OFF→ON
OFF→ON
ON→OFF
ON
OFF→ON
ON
ON
ON→OFF
133
MC1
MC2
MC3
OFF
OFF→ON
(OFF)
(OFF→ON)
ON
OFF
ON
ON
OFF→ON
ON→OFF
ON
ON→OFF
OFF→ON
ON
OFF
ON
PARAMETERS
Remarks
External operation mode
(PU operation mode)
After MC3 switches off,
MC2 switches on.
(Motor coasts during this
period.)
Waiting time 2s.
After MC2 switches off,
MC3 switches on.
(Motor coasts during this
period.)
Waiting time 4s.
4

Advertisement

Table of Contents
loading

Table of Contents