4.2.8 Starting frequency (Pr. 13)

Pr. 13 "starting frequency"
You can set the starting frequency between 0 and 60Hz.
# Set the starting frequency at which the start signal is switched on.
Parameter
Factory Setting
Number
13
0.5Hz
Note: The inverter will not start if the frequency setting signal is less than the value set in Pr. 13 "starting
frequency".
For example, when 5Hz is set in Pr. 13, the motor will start running when the frequency setting signal
reaches 5Hz.
When the Pr. 13 setting is lower than the Pr. 2 value, note that the motor will start
running at the preset speed by merely turning the start signal on, even if the command
frequency has not been entered.
Setting Range
0 to 60Hz
Output frequency
CAUTION
75
PARAMETERS
Related parameters
Pr. 2 "minimum frequency"
(Hz)
60
Pr.13
0
Frequency setting signal (V)
Forward
ON
rotation
Time
4