# You can set the output frequency of the inverter-operated motor at which the commercial power supply
operation motors start. When the output frequency higher than the preset value continues for longer than
the time set in Pr. 515, the commercial power supply motors start. In this case, the starting sequence
depends on the pattern in Pr. 501. Here, the Pr. 509 value means the set value at which the commercial
power supply motors start when the number of commercial power supply motors running is 0.
Parameter Number
509
Auxiliary motor 1 starting frequency
510
Auxiliary motor 2 starting frequency
511
Auxiliary motor 3 starting frequency
# You can set the output frequency of the inverter-operated motor at which the commercial power supply
operation motors stop. When the output frequency lower than the preset value continues for longer than the
time set in Pr. 516, the commercial power supply motors stop. In this case, the stopping sequence depends
on the pattern in Pr. 501. Here, the Pr. 512 value means the set value at which the commercial power
supply motors stop when the number of commercial power supply motors running is 1.
Parameter Number
512
Auxiliary motor 1 stopping frequency
513
Auxiliary motor 2 stopping frequency
514
Auxiliary motor 3 stopping frequency
# You can set the delay time until the auxiliary motor is started. The auxiliary motor starts actually when the
time set in Pr. 515 elapses after the output frequency of the inverter operation motor has risen to or above
the value set in any of Pr. 509 to Pr. 511.
Parameter Number
515
Auxiliary motor start delay time
# You can set the delay time until the auxiliary motor is stopped. The auxiliary motor stops actually when the
time set in Pr. 516 elapses after the output frequency of the inverter operation motor has dropped to or
below the value set in any of Pr. 512 to Pr. 514.
Parameter Number
516
Auxiliary motor stop delay time
# You can set the MC switching interlock time (e.g. time from when RI01 turns off until R01 turns on) when
Pr. 501 = 2.
Parameter Number
502
MC switching interlock time
# You can set the time from MC switch-over to a start (time from when RI01 turns off and RI02 turns on until
inverter output starts) when Pr. 501 = 2. Set this time a little longer than the MC switching time.
Parameter Number
503
Start waiting time
# You can set the deceleration time for decreasing the output frequency of the inverter if a motor connection
occurs under advanced PID control. When the setting is 9999, the output frequency is not forcibly changed.
Parameter Number
Auxiliary motor connection-time
504
deceleration time
# You can set the acceleration time for increasing the output frequency of the inverter if a motor
disconnection occurs under advanced PID control. When the setting is 9999, the output frequency is not
forcibly changed.
Parameter Number
Auxiliary motor disconnection-time
505
acceleration time
Name
Setting Range
0 to 120Hz
0 to 120Hz
0 to 120Hz
Name
Setting Range
0 to 120Hz
0 to 120Hz
0 to 120Hz
Name
Setting Range
0 to 3600s
Name
Setting Range
0 to 3600s
Name
Setting Range
Name
Setting Range
Name
Setting Range
0 to 3600s
Name
Setting Range
0 to 3600s, 9999
154
Setting Increments
0.01Hz
0.01Hz
0.01Hz
Setting Increments
0.01Hz
0.01Hz
0.01Hz
Setting Increments
0.1s
Setting Increments
0.1s
Setting Increments
0 to 100s
0.1s
Setting Increments
0 to 100s
0.1s
Setting Increments
0.1s/0.01s
Setting Increments
0.1s/0.01s
PARAMETERS
Factory Setting
<EC version>
60Hz
<50Hz>
60Hz
<50Hz>
60Hz
<50Hz>
Factory Setting
0Hz
0Hz
0Hz
Factory Setting
5s
Factory Setting
5s
Factory Setting
1s
Factory Setting
1s
Factory Setting
1s
Factory Setting
1s