2.11 Defrost Control

Outline
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than a certain value to finish.
Detail
Conditions for Starting Defrost
Conditions for Canceling Defrost
The judgment is made with outdoor heat exchanger temperature. (6 ~ 22°C)
Function and Control
The starting conditions is determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than 25 minutes of accumulated time pass after the start of the operation, or ending
the previous defrosting.
Frequency
ON
Compressor
OFF
ON
Four way valve
OFF
ON
Fan
OFF
Electronic expansion
valve opening
64 Hz
0Hz
50 sec.
620 sec.
8 sec.
450 pulse
200 pulse
Control Specification
30 Hz
0Hz
PI control
70 sec.
8 sec.
400 pulse
Initial opening
(R18154)