SiBE04-624_B
2.2.4 3-minute Standby
Turning on the compressor is prohibited for 3 minutes after turning it off.
(Except when defrosting.)
2.2.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not activated when defrosting.)
Function and Control
(Hz)
Frequency
D
C
B
A
E
A (Hz)
B (Hz)
C (Hz)
D (Hz)
E (seconds)
F (seconds)
G (seconds)
H (seconds)
: The upper limit of frequencies G and H are the same.
F
G
H
Cooling
Heating
52
48
54
58
78
80
98
98
220
220
140
140
60
60
60
60
Control Specification
(sec.)
Time
(R13906)