Daikin SiBE04-624_B_FTXR-E Service Manual page 102

Wall mounted type e-series
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Note:
1. Be careful not to break the electrode in cleaning.
2. Since the electrode part is electrified in high voltage, be sure to pull out the power supply
92
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Dust or drip of water is
on the streamer unit.
NO
Does the multi-colored
indicator lamp blink about 1
minute after air purifying
operation starts?
YES
Turn off the power supply
(Turn off the breaker).
Is the streamer unit
installed surely.
YES
Check the connector connection
(S52).
Normal?
YES
Is the limit switch normal?
YES
Check the harness.
Broken?
NO
plug or turn the breaker off while cleaning the electrode part. (Touching in electrifying results
in electrical shock.)
YES
NO
NO
* Connect the connector again for
ensuring the connection.
NO
NO
YES
SiBE04-624_B
Clean the streamer unit.
Clean the streamer unit.
Install the streamer unit
surely.
Correct the connection.
Replace the limit switch.
Replace the harness.
Replace the streamer unit
PCB.
(R18121)
Service Diagnosis