2.32 Position Sensor Abnormality

H6
Error Code
Method of Error
A compressor start-up failure is detected by checking the compressor running condition through
the position detection circuit.
Detection
Error Decision
Conditions
Supposed
Causes
Service Diagnosis
When the compressor does not run for 15 seconds after receiving operation start command.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Disconnection of the compressor relay cable
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage is outside the specified range.
Troubleshooting
119