Control Specification; Frequency Control - Daikin SiBE04-624_B_FTXR-E Service Manual

Wall mounted type e-series
Table of Contents

Advertisement

Control Specification

2. Control Specification

2.1

Frequency Control

Outline
Frequency is determined according to the difference between the room thermistor temperature
and the target temperature.
The function is explained as follows.
1. How to determine frequency
2. Frequency command from the indoor unit (Difference between the room thermistor
3. Frequency initial setting
4. PI control
Detail
How to Determine Frequency
The compressor's frequency is determined by taking the following steps.
1. Determine command frequency
2. Determine upper limit frequency
3. Determine lower limit frequency
4. Determine prohibited frequency
54
temperature and the target temperature)
When the shift of the frequency is less than zero (∆F<0) by PI control,
the target frequency is used as the command frequency.
Upper limit frequency
Command frequency
Limit frequency
Initial frequency
Lower limit frequency
PI control
Defrost control
Command frequency is determined in the following order of priority.
1.Limiting defrost control time
2.Forced cooling
3.Indoor frequency command
The minimum value is set as an upper limit frequency among the frequency upper limits of
the following functions:
Compressor protection, input current, discharge pipe temperature, heating peak-cut, freeze-
up protection, defrost.
The maximum value is set as an lower limit frequency among the frequency lower limits of
the following functions:
Four way valve operation compensation, draft prevention, pressure difference upkeep.
There is a certain prohibited frequency such as a power supply frequency.
Dropping function
Input current control, etc.
FMAX
Compressor protection function
Skip control
FMIN
Four way valve operation compensation, etc.
SiBE04-624_B
Upper limit function
Target frequency
Lower limit function
(R18023)
Function and Control