Compressor Lock - Daikin SiBE04-624_B_FTXR-E Service Manual

Wall mounted type e-series
Table of Contents

Advertisement

Troubleshooting

2.24 Compressor Lock

E6
Error Code
Method of Error
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Detection
Error Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.15
Refer to P.138
Turn off the power. Disconnect the
harnesses U, V, and W.
Check No.15
Check with the inverter analyzer.
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
110
Operation stops due to overcurrent.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Compressor locked
Compressor harness disconnected
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Normal?
YES
Emergency
stop without compressor
running?
NO
System shut
down after errors repeated
several times?
YES
∗ Inverter analyzer:
RSUK0917C
NO
YES
NO
SiBE04-624_B
Correct the power supply or
replace the outdoor unit
PCB.
Replace the compressor.
Check the outdoor electronic
expansion valve coil.
Replace it as required.
Replace the compressor.
(R18317)
Service Diagnosis