Installation distances to walls and ceiling

Stand the stove on a floor plate which meets the requirements
laid down on page 76. Measure to make sure that the size of
the floor plate and the distance between the stove and the wall
are at least as great as specified in the diagrams below. Allow at
least 1.0 metre from the stove door to any combustible part of
the building structure or interior fittings.
Combustible wall
*100
240
*895
1035
* Only permissible with extra side window. Please see page 96.
Fire-retardant wall of brick
Fire-retardant wall of
or concrete
brick or concrete
50
282
845
340
292
292
664
Air inlet Ø64
Air inlet Ø64
Air inlet Ø64
Important!
When placing the stove in a corner close to combustible
wall materials or against a wall with a gap of only 305 mm
to combustible materials, an extra side window with a heat-
reflecting surface must always be fitted.
Combustible wall
*305
450
*637
782
Fire-retardant wall of brick
Fire-retardant wall of
or concrete
brick or concrete
Air inlet Ø64
50
382
Combustible roof
340
265
Air inlet Ø64
Air inlet Ø64
520
560
GB
77