Installation distances

C590T
WHEN INSTALLING TURNTABLE (OPTION)
the following installation distances do not apply.
See the separate turntable installation instructions.
Combustible roof
542
INSTALLATION AGAINST COMBUSTIBLE WALLS
Combustible wall
Permitted area for
combustible parts
of the building
400
479
* If the stove is placed on a hearth plate made of glass for example (accessory), the height from the floor is affected by a distance corresponding to the thickness of the hearth plate, for a free standing
glass hearth plate this is 10 mm.
** To prevent discolouration of painted non-flammable walls we recommend that the same side distance as to combustible walls is used.
100
617
Combustible wall
750
The minimum distance in front of the
stove opening to combustible parts of
the building or interior decoration must
!
be at least 1 m.
The dimension diagrams only show
A separate glass hearth plate
the minimum permitted installation
(accessory) increases the
distances for the stove. When connect-
connection height to the
ing to a steel flue, also note the safety
chimney by 10 mm.
distance requirements of the flue. The
safety distance between an uninsulated
flue and a combustible part of the build-
ing should be at least 450 mm.
463
141
A = height from floor to chimney
connection upwards
Ø150
B = height from floor to c/c chimney
connection rear
C = height from floor to air inlet
D = height from floor to lower edge of
32
hatch
E = minimum height to sloped ceiling
from the centre of the chimney
Air inlet Ø67
100
INSTALLATION AGAINST FIREWALLS
800
Fire-retardant wall of
brick or concrete
592
850
Fire-retardant wall of
brick or concrete
179**
450**