Installation Distances - Contura C i41 Installation Instruction

Table of Contents

Advertisement

GB
232

INSTALLATION DISTANCES

Installation distances
Important!
The dimension diagrams only show the minimum permitted
installation distances for the stove. When connecting to a
steel flue, also note the safety distance requirements of
Ext. Ø 150
Utv.
Ø 150
For corner installation, the
rear and side walls must
always be non-combustible,
alternatively both must
be protected by an
external firewall. Material
requirements for firewall
according to the section
"Walls behind" on page 228.
235
500
!
the flue. The minimum distance to combustible parts of the
building or interior decoration in front of the stove must
be at least 1.5 m.
Combustible roof
Brännbart tak
200
655
C i41
Without shelf/ Bench
910
700
!
For placement against
combustible rear walls, a built-
in protective screen (option in
some markets), or an external
firewall that protects the wall
behind is required. Material
requirements for firewalls
according to the section "Walls
behind" on page 228.