MTU MS15027/02E Operating Instuctions page 56

12 v 4000 lx4; 16 v 4000 lx4
Table of Contents

Advertisement

112314 – HI T-Exhaust B4
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112315 – HI T-Exhaust B5
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112316 – HI T-Exhaust B6
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112317 – HI T-Exhaust B7
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112318 – HI T-Exhaust B8
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
56 | Troubleshooting | MS15027/02E 2015-04
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 162).
3. Check valve gear (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 162).
3. Check valve gear (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 162).
3. Check valve gear (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 162).
3. Check valve gear (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 162).
3. Check valve gear (exhaust valves do not close).