1.4540.019 – Position Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.020 – Elec Temp Fail Low
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.021 – FGT Fail Low
Red alarm. Initiated by TecJet.
Cause
Gas temperature before TecJet
is below the preset limit value.
1.4540.022 – Delta P Fail Low
Red alarm. Initiated by TecJet.
Cause
Delta-p from TecJet below the
set limit value.
1.4540.023 – FGP Fail Low
Red alarm. Initiated by TecJet.
Cause
Gas pressure before TecJet is
below the preset limit value.
1.4540.024 – Coil Current Fail Low
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.025 – Position Fail Low
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Check TecJet and configuration.
Corrective action
u Check TecJet and configuration.
Corrective action
u Check TecJet and configuration.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.