Flow Temperature Set Point During Forced Part Load ($); High Limit Thermostat (%) - REMEHA Quinta 30 Technical Information

High-effi ciency condensing boiler
Table of Contents

Advertisement

DHW control stop or boiler modu-
I
lation set point (based on para-
meter #)
DHW control option
J
Variable speed pump
L
HTG cut in ΔT
N
N/a
O
Boiler type
P
Intern
T
Maximum delay time
U
Start point for 0 Volt analog signal 5) (= -50) – 50 °C
Q
End point for 10 Volt analog sig-
Y
nal
Intern
_
Table 09 Settings service level
*NOTE: see Par. 6.1.4 for values over two digits

6.6.1 Flow temperature set point during forced part load ($)

Adjustable from 20 to 90°C, factory default 80°C
This value will prevent the flow temperature exceeding this temperature during the part
load time.

6.6.2 High limit thermostat (%)

Adjustable from 90 to 110°C (!0), factory default 100°C ()0).
This value sets the high limit temperature at which the boiler will shut down in a lock
out condition requiring manual intervention.
Note: this parameter will have an effect on the minimum flow rate requirement, see
Par. 7.4.7.
57117.indd 24
57117.indd 24
Remeha Quinta 30
00 – 30 °C
00 = Three way
valve(port A = HTG,
port B = DHW)
01 = DHW pump
02 = inverted three way
valve (port A = DHW,
port B = HTG)
n/a
1) (= -10°C) – 20 °C
May not be changed!
May not be changed!
00 – 99 minutes
50 – (( (=299) °C
24
20
00
)3
03
10
74
01
15
00
)0 (=100)*
10
1-4-2009 14:35:51
1-4-2009 14:35:51