Flow Temperature Set Point During Forced Part Load; High Limit Thermostat; Fan Speed At Full Load Htg; Fan Speed At Part Load - REMEHA Gas 110 Eco 115 Installation, User And Service Manual

Gas fired condensing boiler
Hide thumbs Also See for Gas 110 Eco 115:
Table of Contents

Advertisement

4.6.1

Flow temperature set point during forced part load ( )

Adjustable from 20 °C to 90 °C.
4.6.2

High limit thermostat ( )

Adjustable from 90 °C to 110 °C (
This value sets the high limit temperature at which the boiler will shut
down in a lock out condition requiring manual intervention.
4.6.3

Fan speed at full load HTG ( )

Adjustable from 18% to 100% output (= approx. 1300 to 7000 rpm for
the 115 and 1200 to 6000 for the 65). This value sets the maximum
output of the boiler.
4.6.4
Fan speed at part load (HTG and DHW -
Adjustable from 18% to 100% output (= approx. 1300 to 7000 rpm for
the 115 and 1200 to 6000 for the 65). This value sets the minimum
output of the boiler.
4.6.5

Starting point modulation ( )

Adjustable from 5 °C to 30 °C.
This value sets the flow/return
modulation begins. If the
∆T
be at minimum output (parameter
(code
)
See chapter 4.4.
4.6.6

Interface selection ( )

Adjustable
or
.
This value sets the control option.
for standard external control.
for Open Therm option.
22
).
point at which the control
∆T
continues to rise, at 40 °C the boiler will
), at 45 °C the boiler will shut off
This value will prevent the flow temperature exceeding this
temperature during the part load time.
* NOTE: this parameter will have an effect on the minimum flow rate
requirement
See chapter 5.3.
)
The factory default should be correct for most installations. Changing
this value should only be carried out on advice from the service
engineer. Do not change the factory default for the minimum output
(parameter
), in cases of minimal flow.
NOTE: Installations with low flow problems would benefit by reducing
this set point to force modulation to begin sooner and minimise boiler
off time.
Gas 110 Eco 115 / 65