Checking The Burner Gasket And Burner Gauze Assembly - Viessmann Vitodens 200-W Installation And Service Instructions For Contractors

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Checking the burner gasket and burner gauze assembly

Check burner gasket
A
for possible damage and replace if required.
E
B
Fig. 24
1. Remove electrodes
B
2. Undo two retaining clips
ring
and then remove thermal insulation ring
D
3. Undo two Torx screws and remove burner gauze
assembly
with gasket
E
4. Insert new burner gauze assembly
gasket
and secure.
F
Torque: 5.0 Nm.
30
and burner gauze assembly
F
E
2x
.
on thermal insulation
C
.
F
with new
E
D
A
2x
C
5. Fit thermal insulation ring
6. Fit electrodes
B
.
Torque: 4.5 Nm.
D
.
D
.