DoorKing 6050-080 Installation And Owner's Manual page 2

Vehicular swing gate operator
Table of Contents

Advertisement

QUICK GUIDE: DIP-Switches
When a switch setting is changed, power must be turned OFF and then turned back ON for the new setting to take affect.
Switch
Function
Circuit
1 and 2
Board
Relay
Exit Loop Port
Output
3
Full Open Input
Auto-Close
4
Timer
5
Not Used
3-Button
6
Single Button
Dual Operators
7
Single Operator
8
Tamper Protect
Switch
Function
Primary
Gate Opening
1
Direction
Secondary
Gate Opening
2
Direction
Not Used
3
Motor Control
4
for Secondary
Operator
Reverse
5
Shadow Loop
Gate Overlap
6
Monitored
7
Photo Sensor
Monitored
8
Reversing Edge
2 Quick Guide - 1
Every time the operator is powered up, the First open command will
automatically set the open and close limits of the gate. (See page 21).
SW 1 (Top 8 Switches)
Setting
1-OFF
2-OFF
Relay activates when gate is open (Shadow loop setting when used).
1-OFF
2-ON
Relay activates when gate is not closed.
1-ON
2-OFF
Relay activates when gate is opening and open.
1-ON
2-ON
Relay activates when gate is opening and closing.
The output wired to terminal #12 becomes the output from the exit loop detector plugged
OFF
into the EXIT Loop port.
Normal Setting. Terminal #12 is a normal full open input.
ON
Auto-close timer is OFF. Manual input required to close gate.
OFF
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.
ON
OFF
Leave in the OFF position.
OFF
OFF when using a 3-button station (DoorKing 3-button control stations only).
ON
ON when using a single button control, terminals 13 &14 become a STOP input.
OFF
Switch must be OFF when bi-parting (dual) gates are used.
Switch must be ON for single operator.
ON
Tamper protect is OFF.
OFF
Normal Setting. Tamper protect is ON. Operator will close gate when being forced open.
ON
SW 2 (Bottom 8 Switches)
Setting
Opens
Clockwise
Same as above, for secondary 6050/6100 ONLY.
OFF
Leave in OFF position.
Switch is OFF when both primary and secondary operator motors are powered from main
OFF
terminals 4 and 5. Applies to operators originally manufactured with 4501, Rev O boards or
lower).
Switch is ON when secondary operator motor is powered from the secondary motor
ON
terminals. Applies to operators manufactured with 4501, Rev P boards and higher, and all
4502 boards.
Terminal 15 is a STANDARD Reverse input.
OFF
Terminal 15 is a Shadow input. Gate will NOT stop during the close cycle.
ON
OFF
Primary and secondary operators start at the same time.
ON
Secondary operator starts 1-2 seconds prior to primary operator.
No Photo Sensor connected to Aux terminal 7 and 8.
OFF
Photo sensor is connected to Aux terminal 7 and 8 and monitored.
ON
No Reversing edge connected to Aux terminal 9 and 10.
OFF
Reversing edge is connected to Aux terminal 9 and 10 and monitored.
ON
See page 20 for descriptions about DIP-switches.
Description
Description
ON
OFF
Opens
Counter-Clockwise
6050-065-C-2-16