Powerware 9330 Installation & Operation Manual page 173

Ibm 9910 ups 20 kva
Table of Contents

Advertisement

1.
The UPS equipment operating environment must meet the size and weight requirements
shown in Table J, according to your UPS system configuration.
2.
In the UPS system, the UPS, Options, and Battery cabinets are palleted separately for
shipping.
3.
Do not tilt cabinets more than
4.
Dimensions are in millimeters (inches).
UPS Cabinet with Filter and Batteries
Options Cabinet with PDM, Distribution
Housing and no transformer
Battery Cabinet
NOTE: For UPS Cabinet without Batteries, subtract 227 Kg (499 lb)
5.
The clearances required around the UPS System are shown in Table K.
From Front of Cabinet
From Back of Cabinet
From Sides of Cabinet
6.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:
Recommended Operating Range: 20---25˚C (68---77˚F)
Maximum Relative Humidity:
The UPS ventilation requirements are shown in Table L.
Table L. Air Conditioning or Ventilation Requirements
Ratings
20 KVA
Powerware 9330 (IBM 9910 20 kVA) Installation and Operation
164201491 REV. B 013004
10˚ during handling.
Table J. Equipment Weight
Table J. Equipment Weight
Powerware 9330 (IBM 9910 20 kVA)
Component
Component
Table K. System ClearancesPowerware
9330 (IBM 9910 20 kVA)
During Full Load Operation
Powerware 9330 (IBM 9910 20 kVA)
Input/Output Voltage
208/208
Shipping
461 (1017)
130 (286)
361 (795)
36 inches working space
36 inches working space
Allow space for Options and Battery Cabinets
0---40˚C (32---104˚F)
95%, noncondensing
Heat Rejection*
BTU/hr ¢ 1000/hr (Kg---cal/hr)
4.2 (1.1)
DESCRIPTION:
PHYSICAL FEATURES AND REQUIREMENTS
DRAWING NO:
164201491---3
REVISION:
A
Weight
Kg (lb)
Installed
Point Loading
435 (958)
6 at 73 (160)
103 (226)
4 at 26 (57)
333 (735)
6 at 56 (123)
SHEET:
DATE:
071503
1 of 1
A ---11