Powerware 9315s Installation & Operation Manual

Powerware 9315s Installation & Operation Manual

Parallel capacity/redundant ups with powerhandler plus switchboard system bypass module (ssbm)
Table of Contents

Advertisement

Quick Links

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 9315s and is the answer not in the manual?

Questions and answers

Summary of Contents for Powerware 9315s

  • Page 2: Important Safety Instructions

    This is a product for restricted sales distribution to informed partners. Installation restrictions or additional measures may be needed to prevent disturbances. ---------------------------------- SAVE THESE INSTRUCTIONS Conserver Ces Instructions concernant la sécurité. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 3: Table Of Contents

    Installing a Remote Monitor Panel Installing a Relay Interface Module Installing a Supervisory Contact Module Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 ..........
  • Page 4 ......Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM ....
  • Page 5 10.3.4 Single UPM Shutdown 10.3.5 SSBM Shutdown to Bypass 10.3.6 Restarting a Single UPM Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 ........
  • Page 6 ....... . Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM .
  • Page 7 Computer Mode 13.9 Remote Monitor Mode Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 ....... . .
  • Page 8 ........... . . Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 14---1...
  • Page 9 Figure 9---5. Versions Screen Figure 9---6. Event History Log Screen Figure 9---7. Active System Events Screen Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 ........
  • Page 10 ........Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM...
  • Page 11: List Of Tables

    Table 13---1. Pin Assignments for Port 1 (DB---9) Table 13---2. Pin Assignments for Port 2 (DB---25) Table 13---3. Options Available for Each Communication Port Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 ....
  • Page 12 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 13: Introduction

    In particular, you should be thoroughly familiar with the Emergency UPM Off procedure described in Chapter 7 of this manual and Emergency Load Off procedure described in the Powerware 9315 UPS Operation manual provided with the UPM.
  • Page 14: Figure 1. Typical Parallel Capacity/Redundant System With Ssbm

    See enclosed switchboard vendor drawings for details. Figure 1. Typical Parallel Capacity/Redundant System with SSBM Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM UTILITY POWER INPUT TO UPM UPM OUTPUT TO SSBM INPUT *See Table N of Appendix A for UPM Output Conductor Sizing.
  • Page 15: Basic System Configurations

    You can enhance any of these system configurations by adding optional accessories, such as a Remote Monitor Panel (RMP), Relay Interface Module (RIM), Supervisory Contact Module (SCM), or Remote Emergency Power Off (EPO) control. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 16: Getting Started 1

    Parallel Capacity/Redundant system features and options. • Chapter 12 -- Responding to System Events -- lists all the alarm, messages and notices that occur during operation of the Parallel Capacity/Redundant system. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 17: Conventions Used In This Manual

    In this manual, the term SSBM refers only to the Switchboard System Bypass Module and its internal elements. The term Parallel Capacity/Redundant system refers to the entire power protection system—the SSBM, UPS modules, battery racks and options or accessories installed. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 18: Safety Considerations

    The system is not intended for outdoor use. • The operating environment should be maintained within the parameters stated in this manual and the Powerware 9315 Operation manual provided with the UPS system. • Keep the cabinet doors closed to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the unit.
  • Page 19: For More Information

    UPS and how to connect optional remote accessories to your UPS system; provides information about enabling, disabling, and customizing building alarms. Contact your local Powerware Field Service office for information on how to obtain copies of this manual. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev.
  • Page 20: Getting Help

    Getting Help If you have a question about any of the information in this manual, or if you have a question this manual does not answer, please call Powerware Corporation Field Service: United States Canada Outside the U.S. viii 1-800-843-9433...
  • Page 21: Section I

    Section I Installation Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 22 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 23: Getting Started

    Inspect, unpack, and unload the UPMs (refer to the applicable Powerware 9315 Installation manual provided with the UPM). Wire the system (refer to Chapter 2 and the applicable Powerware 9315 Installation manual provided with the UPM). Install features, accessories, and/or options, as applicable (Chapter 3).
  • Page 24: Preparing Your Site

    0---25˚C (32---77˚F) 95% noncondensing / 3W system being in a 25_C room ∅ / 4W system being in a 25_C room ∅ Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A / 3W ∅ / 4W ∅ 092402...
  • Page 25 UPM and SSBM terminals. Powerware UPMs are rated for operation in a 40_C room ambient. For this reason, Table O and P are based on the entire 3 in a 40_C room ambient, the use of 90_C copper wire and a 0.80 derating factor because there are more than three current carrying conductors in a raceway (NEC Table 310 ---16 and Notes).
  • Page 26: Inspecting And Unpacking Each Cabinet

    1.1.5 Inspecting and Unpacking Each Cabinet NOTE: Refer to the applicable Powerware 9315 Installation manual provided with the UPMs for UPM unpacking instructions. The first task in preparing for installation is inspecting and unpacking the SSBM. The SSBM is shipped in sections which are bolted to wooden pallets and protected with outer protective packaging material as shown in Figure 1---1 and a plastic inner covering.
  • Page 27 After removing the protective covering, inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact Powerware Corporation Customer Service Department immediately to determine the extent of the damage and its impact upon further installation.
  • Page 28 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 1--6 164201373 Rev. A 092402...
  • Page 29: Preliminary Installation Information

    • Details about control wiring are provided in each procedure for connecting options and features. Drawings 164201373---4 through 164201373---7 in Appendix A identify the control wiring terminations. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 WARNING: 10˚during installation.
  • Page 30: Installing The Switchboard System Bypass Module

    Run section wiring harnesses through wire trough in rear cabling area and pass into Control section through grommeted opening. Insert harness plugs into match caps in the bottom of the A1 Panel in the Control Section. 2--2 WARNING: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 31: Installing Optional System Maintenance Bypass (Smb)

    Connect Mate-N-Lock plug and cap at temporary Load Bank current transformers. Insert harness plugs into matching caps in the bottom of the A1 Panel in the Control Section. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 2--3...
  • Page 32: Installing The Powerware Static Switch

    Installing the Powerware Static Switch Your Switchboard System Bypass Module (SSBM) includes the Powerware static switch shown below. SSBM Current Static Switch Rating Current Rating 2500A 3000 to 4000A 2.4.1 Installing a Fully Rated Static Switch (2500A or 4000A) The SSBM should be shut down prior to installing the static switch.
  • Page 33: Setting The Power+ Trip Unit

    SSBM and SMB circuit breakers trip units. NOTE: The applicable time ---current curve is GE Document GES ---9890E. Installing UPM Cabinets To install the UPMs, refer to the Powerware 9315 UPS Insatallation manual provided with the UPMs. Installing SSBM Wiring NOTE: Refer to section 1.1.4 for additional guidance for wiring and conduit...
  • Page 34: Installing Optional Smb Wiring

    Service personnel may request a copy of the completed Installation Checklist to be sure you have completed all applicable equipment installation. NOTE: The Installation Checklist MUST be completed prior to starting the Parallel Capacity/Redundant system for the first time. 2--6 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 35: 2.12 Installation Checklist

    A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the UPS and battery cabinet. (OPTIONAL) Startup and operational checks performed by authorized service personnel. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 36 Notes ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 2--8 164201373 Rev. A 092402...
  • Page 37: Figure 3---1. Remote Epo Control

    Figure 3---1. Remote EPO Control NOTE: Before installing an Remote EPO, be sure you have prepared the SSBM according to the instructions in Chapter 2. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 UNINTERRUPTIBLE POWER SYSTEM...
  • Page 38 Secure the SSBM by reversing all steps taken to prepare it for Remote EPO installation. 3--2 To Customer Interface Panel in SSBM TB2---1 TB2---2 Table 3---2. Remote EPO TWISTED WIRES (2) Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM Remarks Twisted wires (2) Twisted wires (2) 14---18 gauge 164201373 Rev. A 092402...
  • Page 39: Installing A Remote Monitor Panel

    164201373---8 in Appendix A shows the enclosure dimensions and knockout patterns. Table 4---1. Optional Monitoring Accessories Number and Type of Accessories Permitted Remote Monitor Panel — — — Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 Relay Interface Module Supervisory Contact Module — — —...
  • Page 40: Figure 4---1. Remote Monitor Panel (Rmp)

    Figure 4---1. Remote Monitor Panel (RMP) 4--2 FLUSH MOUNT WIRES MUST BE TWISTED Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A SURFACE MOUNT (FOR HANGING) 092402...
  • Page 41: Figure 4---2. Terminal Block Bracket

    Customer Interface Panel. Connect to Port 1 (DB---9) on Customer Interface Panel Figure 4---2. Terminal Block Bracket Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 FUSE TERMINAL BLOCK...
  • Page 42 1---2 TURNS PER TB3---3 3 INCHES 3 INCHES TB3---4 To SSBM Remarks TB3---5 TWISTED WIRES (4) TB3---6 1---2 TURNS PER 1 2 TURNS PER TB3---7 3 INCHES 3 INCHES TB3---8 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 43: Installing A Relay Interface Module

    CONNECTORS Figure 5---1. Relay Interface Module NOTE: Before installing an RIM, be sure you have prepared the SSBM according to the instructions in Chapter 2. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 FLUSH MOUNT Relay Interface Module...
  • Page 44: Figure 5---2. Terminal Block Bracket

    Customer Interface Panel. Connect to Port 1 (DB---9) on Customer Interface Panel Figure 5---2. Terminal Block Bracket 5--2 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A FUSE TERMINAL BLOCK (TB3) 092402...
  • Page 45 4 or 6, respectively; otherwise, secure the SSBM by reversing the steps contained in procedure “To Prepare the SSBM for Wiring to an RMP , RIM, SCM, or Remote EPO” of Chapter 2. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 Table 5---1.
  • Page 46 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 5--4 164201373 Rev. A 092402...
  • Page 47: Rev. A

    Figure 6---1. Supervisory Contact Module NOTE: Before installing an SCM, be sure you have prepared the SSBM according to the instructions in Chapter 2. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 SURFACE MOUNT (FOR HANGING)
  • Page 48: Figure 6---2. Terminal Block Bracket

    Customer Interface Panel. Connect to Port 1 (DB---9) on Customer Interface Panel Figure 6---2. Terminal Block Bracket 6--2 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A FUSE TERMINAL BLOCK (TB3) 092402...
  • Page 49 Chapter 4 or 5, respectively; otherwise, secure the SSBM by reversing the steps contained in procedure “To Prepare the SSBM for Wiring to an RMP , RIM, SCM, or Remote EPO” of Chapter 2. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 50 IMMINENT Note: Supervisory contacts are rated at 2.0 amps at 28 Vdc or 120 Vac and 0.15 amp at 115 Vdc. Supervisory contacts require external power supply. Internal 24 Vdc is not capable of supplying contact current. Figure 6---3. Supervisory Contact Module TB2...
  • Page 51: Operation

    Section II Operation Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 52 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 53: Understanding Parallel Capacity/Redundant System Operation

    (such as a generator) or shut down the critical load in an orderly manner. Refer to the Powerware 9315 Operation manual provided with the UPMs for operation of the UPMs.
  • Page 54 PowerNets. Failure of one of the two will only result in an alarm condition. In addition, the applications at each node are designed such that messages can be lost on the network without affecting the operation of the system. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 7--2 164201373 Rev. A...
  • Page 55: Battery Mode 7

    In Bypass mode, the SSBM bypass input supplies the load and isolates the UPMs. • In Battery mode, the battery cabinet supplies DC power, which maintains UPM operation. The following descriptions provide the Parallel Capacity/Redundant system operating mode differences. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 7--3...
  • Page 56: Normal Mode

    7--4 SSBM UPM1 (open) UPM2 UPM3 UPM4 in Normal Mode. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM BYPASS INPUT OUTPUT TO CRITICAL LOAD Path of Electrical Power 164201373 Rev. A 092402...
  • Page 57: Bypass Mode

    Bypass mode is a normal operating mode, and not an alarm condition. However, if the SSBM is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition will be recorded. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 58: Battery Mode

    Normal mode is achieved. 7--6 SSBM UPM1 (open) UPM2 UPM3 UPM4 System in Battery Mode Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM BYPASS INPUT OUTPUT TO CRITICAL LOAD Path of Electrical Power 164201373 Rev. A 092402...
  • Page 59: Load Bank Mode

    With the rear door open, personnel are exposed to energized buswork. To prevent injury from electrical shock, temporary barriers and warning signs should be established. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 WARNING:...
  • Page 60 Load Bank Mode with SSBM with Temporary Load Bank Tabs. 7--8 SSBM UPM1 (open) UPM2 UPM3 TEMP. UPM4 TO TEMPORARY LOAD BANK (BY OTHERS) Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM BYPASS INPUT TABS OUTPUT TO CRITICAL LOAD 164201373 Rev. A 092402...
  • Page 61 BATT Path of Electrical Power Figure 7---5. Path of Current Through the Parallel Capacity/Redundant System in Load Bank Mode with SSBM/SMB with Temporary Load Bank Tabs. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 SSBM UPM1...
  • Page 62: Maintenance Bypass Mode (Optional) 7

    SSBM automatically closes the MBP breaker to maintain power to the critical load. The following descriptions provide the Parallel Capacity/Redundant system optional operating mode differences. 7--10 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 63: Maintenance Bypass Mode (Optional)

    Capacity/Redundant system when operating in Maintenance Bypass mode. INPUT BATT BATT BATT BATT Path of Electrical Power Figure 7---6. Path of Current Through the Parallel Capacity/Redundant System Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 CAUTION: SSBM UPM1 UPM2 UPM3 UPM4 in Maintenance Bypass Mode.
  • Page 64: Redundant Cbp Mode (Optional)

    Maintenance Bypass mode to Bypass mode as described above. Figure 7---7 shows the path of electrical power through the Parallel Capacity/Redundant system when operating in Maintenance Bypass mode. 7--12 CAUTION: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 65 INPUT BATT BATT BATT BATT Path of Electrical Power Figure 7---7. Path of Current Through the Parallel Capacity/Redundant System Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 SSBM UPM1 (open) UPM2 (open) UPM3 UPM4 in Redundant CBP Mode.
  • Page 66 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 7--14 164201373 Rev. A 092402...
  • Page 67: Operational Controls And Features

    NOTE: Read the Operation section and have thorough knowledge of Parallel Capacity/Redundant operation before attempting to operate. For a more detailed description of UPS operation, refer to Powerware 9315 Operation manual supplied with the UPS system. SSBM Standard Features...
  • Page 68: Figure 8---1. Typical Ssbm Control Section (Sheet 1 Of)

    CONTROL/MONITOR PANEL FRONT VIEW 110915520 Figure 8---1. Typical SSBM Control Section (Sheet 1 of 4) 8--2 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 69: Figure 8---1. Typical Ssbm Control Section (Sheet 2 Of)

    SMB ELECTRICAL INTERLOCK (A10) SMB ELECTRICAL INTERLOCK WITH REDUNDANT CBP (A11) 110915520 Figure 8---1. Typical SSBM Control Section (Sheet 2 of 4) Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 NETWORK POWER SUPPLY PANEL (A13) FRONT VIEW...
  • Page 70: Figure 8---1. Typical Ssbm Control Section (Sheet 3 Of)

    CUSTOMER INTERFACE PANEL POWERNODE PANEL (OPTIONAL) 110915520 Figure 8---1. Typical SSBM Control Section (Sheet 3 of 4) 8--4 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 71: Figure 8---1. Typical Ssbm Control Section (Sheet 4 Of)

    SMB ELECTRICAL INTERLOCK PANEL (A10) (OPTIONAL) SMB ELECTRICAL INTERLOCK PANEL (A11) WITH REDUNDANT CBP CONTROLS (OPTIONAL) 110915520 Figure 8---1. Typical SSBM Control Section (Sheet 4 of 4) Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 8--5...
  • Page 72: Smb Circuit Breakers

    Class 1 wiring methods. Class 1 wiring can be routed through the top or bottom of each cabinet. 8--6 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 73: Options And Accessories

    8.3.4 ModBus Cards The Powerware ModBus Card is an optional X---Slot connectivity device that allows you to continuously and reliably monitor the UPS system in your Building Management System (BMS). See Powerware ModBus Card User Guide 164201376, and Powerware Expansion Chassis User Guide, 164201336 for details.
  • Page 74: Safety Considerations

    • Always conform to the more detailed safety precautions described in “Important Safety Instructions” section of Chapter 15. 8--8 WARNING: Parallel Capacity/Redundant system Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 75: Symbols, Controls, And Indicators

    Stop and refer to the Operator’s Manual for more information. RISK OF ELECTRIC SHOCK There is a risk of electric shock present, and you should observe associated warnings. The UPS contains high voltages. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 8--9...
  • Page 76 This Page Intentionally Left Blank. 8--10 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 77: Using The Control Panel 9

    (4) a vertical column of backlit status indicators, (5) a SYSTEM MODE key switch, (6) a PUSH IN TO RESET pushbutton. The following sections describe the Monitor Panel in detail. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 PUSH IN...
  • Page 78: Using The Lcd Screen 9

    9--2 Uninterruptible Power System Input FREQ 60.0 0.95 Bypass Setup Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 15 JUL 1998 09:25:42 Output FREQ 60.0 0.80 Battery pushbuttons pushbuttons to move the highlight 164201373 Rev.
  • Page 79: Adjusting The Contrast 9

    Use the pushbuttons to adjust the contrast on the LCD screen. Hold down the pushbutton, then press the pushbutton to decrease the contrast. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 pushbuttons to move through the options in a menu, or to...
  • Page 80: Reading The Status Indicators 9

    Normal mode, at which point the Normal indicator is lit. During normal shutdown, the Standby indicator is lit until all energy in the UPS is dissipated and shutdown is complete. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM pushbuttons and the 164201373 Rev. A...
  • Page 81: Using The Menu Options 9

    UPS. The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V) and the DC current (I). Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 82: Load Amp Meters Screen 9

    Events Statistics Graphics Setup Figure 9---4. Load Amps Meters Screen 9--6 Uninterruptible Power System Output Current 125% 100% Phase A Phase B Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 15 JUL 1998 09:25:42 Phase C 164201373 Rev. A 092402...
  • Page 83: Software Versions Screen 9

    NOTICES: NONE Battery Minutes 48.5 Meter History System Loading Versions Events Meters Statistics Graphics Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 Uninterruptible Power System Software Versions Version Part Number Monitor 01.17 143650369 Rectifier ***** 143650347...
  • Page 84: System History Screen 9

    STATUS: Bypass Contactor (K4) 16:41:29.1 STATUS: Inverter Normal Statistics Graphics Setup ) appears in the upper right corner of the information area Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 15 JUL 1998 09:25:42 Open pushbuttons 164201373 Rev. A 092402...
  • Page 85: Active System Events Screen 9

    48.5 Events History Active Versions Events Meters Statistics Graphics Figure 9---7. Active System Events Screen Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 Uninterruptible Power System SHUTDOWN IMMINENT Active System Events NOTICE: Input power unavailable NOTICE:...
  • Page 86: Unit Statistics Screen 9

    Building Alarm 3 Building Alarm 4 Building Alarm 5 Building Alarm 6 Graphics Setup Figure 9---8. Unit Statistics Screen Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 15 JUL 1998 09:25:42 04 MAY 1997 Time On: DAYS HR MN 0035 20 59...
  • Page 87: Mimic Screen 9

    Mimic screen is dependent on the actual number of units installed at location. Also all alarms are shown for information purposes only. Only actual alarms would be shown in the installed instance. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 88: Time Setup Screen 9

    MON 07 Setup Figure 9---10. Time Setup Screen ) appears in the upper right corner of the Time Setup pushbutton. If you want to save the Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 15 JUL 1998 09:25:42 HR:MN SAVE...
  • Page 89: Port Setup Screen 9

    SAVE field is set to YES. The setup screens for Port 1 and Port 2 are identical. For detailed information about configuring the serial ports, refer to Chapter 13, “Serial Communications.” Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 90 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 9--14 164201373 Rev. A 092402...
  • Page 91: Initial Setup 10

    2. Refer to Chapter 9 of this manual for description of SSBM controls and monitor panel functions. 3. Refer to the applicable Powerware 9315 UPS Operation manual provided with the UPMs, for UPM operating instructions. 10.2 Operation of SSBM with Powerware 9315 ---200 thru 9315 ---500 UPMs 10.2.1...
  • Page 92: Manual Start 10

    Observe that breaker CBS closes and breaker CBP opens. System is now in Normal mode, with the critical load being supplied power from the UPMs. 10--2 is in Bypass mode and Normal mode. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 93: Auto Start

    NOTE: If transfer is not completed within one minute, the SYSTEM MODE key switch must be turned momentarily to NORMAL again to achieve normal operation. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 10--3...
  • Page 94: Ssbm Shutdown To Bypass 10

    Fans and load side of K3 will still have voltage present. WARNING: upstream UPM input feeder circuit Fans and load side of K3 will still have voltage present. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 95: Restarting A Single Upm 10

    “Resetting the UPM after Load Off” of this chapter before starting the UPS. NOTE: The UPM Remote Emergency Load Off option functions the same way as the LOAD OFF pushbutton on the Monitor Panel. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 96: Resetting The Upm After Load Off

    TRIPPED position. The UPM is now reset. To restart the UPM , follow the procedure in Chapter 4, “Starting and Stopping the UPS” in the applicable Powerware 9315 UPS Operators manual provided with the UPM.
  • Page 97: To Use The Ssbm Emergency Upm Off Pushbutton 10

    The Parallel Capacity/Redundant system is now reset. To restart the Parallel Capacity/Redundant system, follow the procedure at the beginning of this Chapter. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 PUSH IN TO RESET pushbutton on the SSBM Control Panel...
  • Page 98: Initial Setup 10

    Observe all UPM monitor screens become active as an indication of logic power. Verify all UPMs are shown on the SSBM mimic screen. 10--8 OPEN OPEN OPEN CLOSED (optional) OPEN (optional) Open Open Open Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 99: Manual Start 10

    If message appears, turn the SSBM SYSTEM MODE key switch to NORMAL momentarily. Observe that breaker CBS closes, breaker CBP opens, and the SSW is turned off. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 10--9...
  • Page 100: Single Upm Shutdown

    Power is present at UPM CB1 input, until breaker is opened. The 10--10 WARNING: upstream UPM input feeder circuit load side of CB3 will still have voltage present. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 101: Ssbm Shutdown To Bypass 10

    Normal mode. If UPS is not in Autorestart, turn the MODE key switch to NORMAL for three seconds to transfer to Normal mode. The UPM is now operating in Normal mode. On SSBM mimic screen, check for presence of UPM. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 WARNING: upstream UPM input feeder circuit breaker is opened.
  • Page 102: To Use The Upm Emergency Upm Off Pushbutton 10

    The UPM is now reset. To restart the UPM, follow the procedure in this chapter, “Restarting a Single UPM.” 10--12 PUSH TO RESET pushbutton on the UPM Control Panel CAUTION: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 103: To Use The Ssbm Emergency Upm Off Pushbutton 10

    The critical load is transferred to bypass and UPMs powered down. UPM CB1 breakers trip and the UPM is cut off from utility power. This function requires additional EPO kit available from Powerware. Power to the critical load is de-energized and UPMs powered down.
  • Page 104 The Parallel Capacity/Redundant system is now reset. To restart the Parallel Capacity/Redundant system, follow the procedure at the beginning of this chapter. 10--14 CAUTION: Emergency UPM Off Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM until the cause 164201373 Rev. A 092402...
  • Page 105: Operation With Electrical Controls

    Observe MBP closes and MIS opens. System is now on maintenance bypass. To shutdown SSBM and UPMs, follow procedure under SSBM Shutdown to Bypass. On SSBM, open CBP and FBP breakers. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 CAUTION:...
  • Page 106 (FROM MAINTENANCE) momentarily. Observe MIS closes and MBP opens. System is now in bypass mode. 10--16 WARNING: feeder circuit breaker is opened. WARNING: feeder circuit breaker is opened. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 107 CBP repairs and then, proceed to step 3 below. After the CBP breaker has been repaired, the UPS system can be transferred from Maintenance Bypass mode to Bypass mode as described above. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 108 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 10--18 164201373 Rev. A 092402...
  • Page 109: General Purpose Relay Contacts

    Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You should use twisted pair wires for each alarm input and common. If the SSBM is equipped for a Powerware Sync Control, Hot-Tie Control, or continuous duty static switch, not all Building Alarms will be available for customer use.
  • Page 110: Remote Monitor Panel

    Table 11---1. Optional Monitoring Accessories Number and Type of Accessories Permitted Remote Monitor Panel — — — 11--2 Relay Interface Module Supervisory Contact Module — — — Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM — — — 164201373 Rev. A 092402...
  • Page 111 The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This light is accompanied by an audible alarm horn. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 11--3...
  • Page 112: Relay Interface Module

    (pins 6 and 15) Contacts are closed when Utility Failure is detected. (pins 5 and 14) Contacts are closed when approximately 2 minutes of battery time is remaining, before the critical load is lost. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 113: Supervisory Contact Module

    UPS ALARM • ON BYPASS • SHUTDOWN IMMINENT Refer to the applicable Powerware 9315 Installation manual chapter, Installing a Supervisory Contact Module, for TB2 contact configurations. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 TB2---1 through TB2---3...
  • Page 114: External Battery Disconnect For Common Battery Racks

    11.8.1 ModBus Cards The Powerware ModBus Card is an optional X---Slot connectivity device that allows you to continuously and reliably monitor the UPS system in your Building Management System (BMS). See Powerware ModBus Card User Guide 164201376, and Powerware Expansion Chassis User Guide, 164201336 for details.
  • Page 115: Responding To System Events

    Select Active from the Events menu on the LCD screen to look at the Active System Events screen. This screen shows any currently active alarms, notices, or commands. NOTE: Refer to the applicable Powerware 9315 UPS Operation manual provided with the UPMs, for UPM system events. 12.2 System Event Horns The system event horn beeps according to the type of event it is signifying: •...
  • Page 116: System Event Messages

    Check Unit Setup Bypass Contactor (K4) Fail Battery Ground Fault 100% Overload Shutdown 125% Overload Shutdown Over Temperature Shutdown Network Sync Failure Inverter Calibration Required Inverter Setup Required 12--2 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 117 Check Parallel Setup Parallel System Overload On Battery more than 30 Seconds Check UPM Breaker (CBS) AUX Check Bypass Breaker (CBP) AUX Monitor Calibration Required Monitor Setup Required Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 12--3...
  • Page 118 PowerNet Channel B TX Down STSW NOT Available STSW SCR SHORTED Load Over 100% Load Over 125% STSW Disconnected K1 Relay Failure PowerNode Calibration Required PowerNode Setup Required Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 12--4 164201373 Rev. A 092402...
  • Page 119 UPM 2 Phone Home UPM 3 Phone Home UPM 4 Phone Home UPM 5 Phone Home UPM 6 Phone Home UPM 7 Phone Home UPM 8 Phone Home Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 12--5...
  • Page 120 Power Supply Under Voltage Input Transient DC Voltage Low DC Voltage High Equalizing Battery Testing Battery Battery Test Failed Input/Battery Current Limit Reduced Input Current Limit Rct. Logic Power Failure 12--6 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 121 Building Alarm 6 Active Testing Battery Battery Test Aborted (load) Battery Test Aborted (utility) Battery Passed Test ##Printing Sampled Data Other UPS Bypass Not Available Loss of Redundancy Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 12--7...
  • Page 122 Bypass Under Frequency Bypass is Not Available Not Enough UPMs System NOT Redundant PowerNode Calibration Fail PowerNode Calibration Pass No Bypass Sync Check EPO Reset Pn. Logic Power Failure Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 12--8 164201373 Rev. A 092402...
  • Page 123: Connecting Equipment To A Serial Port

    Serial Communications 13.1 Description This chapter describes the serial communications feature of the Powerware 9315 Switchboard System Bypass Module (SSBM). Two serial communications ports on the SSBM allow you to connect equipment to view system event information. The following sections describe the serial communications feature, and provide information about connecting hardware, setting up the ports, changing settings, and changing modes.
  • Page 124: Figure 13

    + 24 volts DC Transmit Data Input to UPS Receive Data Output from UPS Return RS485 + Data RS485 --- Data Return Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM NOT USED 485 + 485 -- RETURN Comments 164201373 Rev. A 092402...
  • Page 125: Figure 13

    Figure 13---2. Port 2 Pin Assignments Table 13---2. Pin Assignments for Port 2 (DB---25) Pin # Symbol +12V ---12V Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 PORT 2 (DB- -25) NOT USED RS232 TXD NOT USED...
  • Page 126: Figure 13---3. Setup Serial Port 1 Screen

    Data/Stop TERMINAL 9600 Setup ) appears in the upper right corner of the Setup Port pushbutton to toggle to the Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 15 JUL 1998 09:25:42 Handshaking Save XON / XOFF pushbutton on the pushbutton.
  • Page 127 300 baud is not recommended for any mode except Remote Monitor. You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19,200. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 128: Default Settings

    Each communications port on the SSBM operates in one of five modes which you select when configuring the port using the Setup Port screen. 13--6 300 baud 8/1 Handshaking Disabled 9600 baud 8/1 Handshaking Disabled Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 129: Printing Selected Information

    Ctrl+A Prints all system information Ctrl+B Prints Battery Test Log To use a key combination, hold down the Control key and press the letter key. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 :::: Description Month (3 letters)
  • Page 130: Entire Log (Ctrl + P)

    Inverter Contactor (3) Closed STATUS: Bypass Contactor (K4) Open STATUS: Inverter Normal NOTICE: Room High Temperature Figure 13---4. Event History Log Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 03 NOV 1997 14:23:45 0421 1000 2030 2202 4001 164201373 Rev. A...
  • Page 131: System Information Printout (Ctrl + A)

    This key sequence prints a listing of all available serial data. This printout contains the information shown on the Event History Log and Meters screens of the SSBM (both Figures 13---4 and 13---5). Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 132: Program Building Alarms 13

    If 1 is entered at the prompt, you can program the building alarm functions: Program Building Alarms 1. Enable/Disable Default Functions 2. Customize Alarm Messages 3. Return to Main Menu Enter Selection: 13--10 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 133: Enable/Disable Default Functions 13

    Enter Selection: The line following the Enabled Building Alarm Number(s) label indicates which building alarms are currently enabled. (In this example, Building Alarms 1 and 4 are enabled.) Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 13--11...
  • Page 134: Customize Alarm Messages

    If an E is entered at the prompt, the custom messages will be used for the building alarm. If a D is entered, the default messages will be used for the building alarm. 13--12 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 135: Program Unit Name

    NOTE: Password must be six characters in length. <CR> to return with no change. The password will be changed if the user enters and verifies the password. The entry must be six characters. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 13--13...
  • Page 136: Battery Test Setup 13

    No Battery Test Scheduled Enter <CR> to return to Battery Test Setup Menu NOTE: The unit will only perform one battery test in any 24 hour period. 13--14 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 137: Modify Low Battery Time

    For a list of products available, contact your sales representative. 13.9 Remote Monitor Mode This mode provides the interface for the RMP , RIM, or SCM described earlier. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 13--15...
  • Page 138 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 13--16 164201373 Rev. A 092402...
  • Page 139: Remote Notification

    Numeric paging support allows the SSBM to call a paging service and send numeric messages. The Housekeeping function maintains the link between the SSBM and modem. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 14--1...
  • Page 140: Remote Notification Features

    • Uses standard modems and null modem cables available at your local computer supply center. NOTE: Programmable functions are to be set by Powerware Corporation authorized personnel only. 14.3 Description of Operation The Remote Notification option performs three basic functions: Call Answer into Terminal mode, Call Out to a remote terminal, and Housekeeping.
  • Page 141: Call Out

    The Call Out process can be terminated at any time by calling into the SSBM and sending the reset command (press and hold [CTRL] and press [R]) or by turning the key switch on the front of the SSBM. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 142: Hardware Requirements

    An alternative to purchasing a cable is to build your own serial cable using the following pin out description: Male DB25 pin 7 pin 2 pin 3 14--4 Male DB25 pin 7 pin 2 pin 2 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 143: Basic Modem Configuration

    The basic modem should be a plug and play type. All setup is done by the UPS. Only the initial phone number needs to be entered by the user. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A...
  • Page 144: Configuring The Modem To Call A Remote Computer

    NOTE: To set up a group one or group two pager number, refer to “Configuring the Modem to Call a Numeric Pager” section of this chapter. 14--6 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 145: Configuring The Modem To Call A Numeric Pager

    NOTE: To set up a group one or group two number to call a computer, refer to “Configuring the Modem to Call a Remote Computer” section of this chapter. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 Keying in the “#”...
  • Page 146: Final Modem Configuration

    9. Key in [A], [T], [&], [W], [0] (zero), then press [ENTER]. 10. Confirm that the modem responds with “OK” or “0” (zero). 14--8 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 147: Ssbm Setup Configuration

    “Serial Communications”). If using a standard serial cable, a null modem adapter is required for the connection to the modem. The Powerware 9315 SSBM can only use serial Port 2, DB---25F, for the Remote Notification option. This connection is located on the Customer interface Panel at the top right of the SSBM cabinet.
  • Page 148: User Selected Events

    Battery DC Under Voltage Battery Discharged Battery Not Charged Battery Voltage Low Phase A Current Limit Phase B Current Limit Phase C Current Limit Phase C Current Limit Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM Group Group 164201373 Rev. A 092402...
  • Page 149 Rectifier DC Over Voltage Rectifier DC Under Voltage Rectifier Failure Rectifier Setup Required Temperature Sensor Failure Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 RECTIFIER Group Group MESSAGES -- NOTICES Battery Test Failed DC Voltage High...
  • Page 150 Power Off Switch Rectifier Network Down Testing Battery Three Wire AC Over Voltage Three Wire AC Under Voltage Three Wire Over Freq. Three Wire Under Freq. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM Group Group 164201373 Rev. A 092402...
  • Page 151: Maintaining The Parallel Capacity/Redundant System

    Regular routine checks of operation and system parameters will enable your system to function efficiently for many trouble-free years. NOTE: Refer to the applicable Powerware 9315 Operation manual provided with the UPS for UPS maintenance.
  • Page 152 L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet. 15--2 WARNING: HAZARDOUS WASTE. Do not incinerate or dispose of batteries WARNING: fire. Observe proper precautions. ATTENTION: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 153: Performing Preventive Maintenance

    Capacity/Redundant system. Contact your nearest Powerware field service office for more information about service offerings. BATTERY maintenance: Contact your nearest Powerware field service office for battery maintenance. Battery replacement and maintenance should be performed only by authorized service personnel. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev.
  • Page 154: Maintenance Training

    PowerBreakII Circuit Breakers/DrawOut 800 ---4000 Ampere Frames, for recommended circuit breaker maintenance. 15.6 Maintenance Training A basic training course, available from Powerware Corporation, gives you a competent working knowledge of the Parallel Capacity/Redundant system operation and teaches you how to perform first level corrective maintenance.
  • Page 155: Product Specifications

    SSBM. 16.2 SSBM Input Input Voltage (UPM Dependent) Input Frequency Range Input Current Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 System 208 VAC nominal (60 Hz only) 220 VAC nominal (60 Hz only) 380 VAC nominal (50/60 Hz)
  • Page 156: Environmental Specifications

    Meets FCC Regulation 47, Part 15, Subpart J, for class A devices Meets IEC 801---2 specifications. Withstands up to 25 kV without damage and with no disturbance or adverse effect to the critical load. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 157: Rev. A

    164201373---11 • 164201373---12 • 164201373---13 • 164201373---14 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 Installation Notes Typical Parallel Capacity/Redundant System with SSBM Oneline Drawing of Typical Parallel Capacity/Redundant System SSBM Customer Interface Panel UPM PowerNet Interface Panel:...
  • Page 158 AWG or kcmil(ea) AWG or kcmil(ea) AWG or kcmil(ea) AWG or kcmil(ea) DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM Rating 2500 3000 4000 2500 3000 4000 Refer to Table R for minimum conductor sizes. Rating...
  • Page 159 The SSBM can be equipped for separate input feeds for the SSBM Bypass input and the SMB Bypass input or for a single input feed for both the SSBM Bypass Input and the SMB Bypass Input. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 160 12 --- 2 bolt mounting *Neutral 24 --- 2 bolt mounting Ground 28 --- 1 bolt mounting DESCRIPTION: INSTALLATION NOTES DRAWING NO: 164201373---1 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM Tightening Bolt/Int. Torque Hex Size N-M (lb-ft) (In.) 76 (56) 76 (56)
  • Page 161 Frame Ground NOTES: * = These neutral bolt mountings are only available on SSBMs or SSBMs with SMBs rated as 3P/4W. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 Powerware 9315 SSBM Model: 4000 Number of Cable...
  • Page 162 A ---6 SSBM Bypass SMB Bypass d S t 2500 2500 SSBM 10˚during handling. ¦ DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM SSBM Model 2500 3000 2500 3000 2500 3000 SSBM Model 3000 4000 All Models...
  • Page 163 6 inches (152mm) and 12 inches (305mm) from the line terminals with five wraps. Wrap each additional 6 inch (152.4mm) interval with five wraps or 1 inch (25.4mm) intervals with one wrap. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 0---25˚C (32---77˚F)
  • Page 164 DESCRIPTION: REDUNDANT SYSTEM WITH SSBM DRAWING NO: 164201373---2 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM *See Table O of Appendix A for UPM Output Conductor Sizing. SSBM INTERFACE - - TERMINAL BLOCK TB1 UPM INTERFACE - - TERMINAL BLOCK TB1...
  • Page 165 4. Actual SSBM physical arrangement and cable connection locations may differ from that shown. See drawings 164201373 ---11 and 164201373 ---12 for details. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 UTILITY POWER INPUT TO UPM UPM OUTPUT TO SSBM INPUT...
  • Page 166 E1- -E3 E4- -E5 E4- -E5 E9- -E12 CAPACITY/REDUNDANT SYSTEM DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM AC INPUT TO AC INPUT TO SYSTEM BYPASS MAINT. BYPASS 3 PHASE, 3 PHASE, 3 OR 4 WIRE 3 OR 4 WIRE...
  • Page 167 AC OUTPUT TO SSBM, 3 PHASE, 4 WIRE (SEE NOTES 2 AND 3) COMMON BATTERY PARALLEL CAPACITY/REDUNDANT SYSTEM See Sheet 3 for notes. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 AC INPUT TO AC INPUT TO...
  • Page 168 Table H. Minimum Size Copper Bonding Jumper SSBM Model 2500A 3000A 4000A DESCRIPTION: ONELINE DRAWINGS OF TYPICAL PARALLEL CAPACITY/REDUNDANT SYSTEM DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM Wire Size (kcmil) SHEET: 164201373---3 164201373 Rev. A 3 of 3 092402...
  • Page 169 Terminate each redundant PowerNet network at the end modules in the system. Use a 120 ohm, 1/4 watt, 5% resistor (Powerware Part Number 141202041). Refer to sheet 2 for typical termination points. If SSBM is to be terminated, install terminating resistors onto terminal block TB1. Refer to sheet 3 for terminal location.
  • Page 170 TYPICAL POWERNET NETWORK WIRING AND TERMINATIONS A ---14 Arrangement A SSBM Arrangement B Arrangement C (Robust Network Routing) DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM CHANNEL B TERMINATION POINTS SSBM CHANNEL B TERMINATION POINTS CHANNEL B...
  • Page 171 SSBM and UPM PowerNet Interface Terminal Block Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 Channel B Channel A Terminating Resistor Terminating Resistor 120 ohm, 1/4 watt, 5% 120 ohm, 1/4 watt, 5% Terminating Resistor Location...
  • Page 172 Sync Reference Voltage for Optional Sync Control, Hot-Tie Control or Hot-Tie with Sync Control Optional CAN Power Supply Panel (A13) Terminal Block for Powerware 9315 (500 kVA ---750 kVA) Models only DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM...
  • Page 173 #2 are used for the MIS and MBP breakers shown on the Monitor Panel Mimic and are unavailable for customer use. If the SSBM is setup for Powerware Sync Control, Building Alarm #4 is used for the “Sync Control Trouble” alarm and is unavailable for customer use.
  • Page 174 Relay 1 is normally deenergized and is only energized for an alarm condition. Relay 2 is normally energized and is only deenergized for an alarm condition. If the SSBM is setup for a Powerware Sync Control, the ON BYPASS contact is used for Sync Control and is not available for customer use.
  • Page 175 Terminate each redundant PowerNet network at the end modules in the system. Use a 120 ohm, 1/4 watt, 5% resistor (Powerware Part Number 141202041). Refer to drawing 164201373---4, sheet 2 for typical termination points. Install terminating resistors onto appropriate UPM PowerNet Interface Panel terminal block.
  • Page 176 Powerware 9315 (200 kVA---300 kVA) PowerNet Interface Panel Location A ---20 INTERFACE PANEL UPM POWERNET INTERFACE PANEL: DESCRIPTION: POWERWARE 9315-- 200 TO -- 500 UPMs DRAWING NO: 164201373---5 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM SHEET: 2 of 4 164201373 Rev.
  • Page 177 Powerware 9315 (400 kVA---500 kVA) PowerNet Interface Panel Location Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 INTERFACE PANEL DESCRIPTION: UPM POWERNET INTERFACE PANEL: POWERWARE 9315-- 200 TO -- 500 UPMs DRAWING NO: 164201373---5 SHEET: 3 of 4...
  • Page 178 EPO to UPM (Optional) Name NOT USED NOT USED DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM Terminal Function Description Channel A connection of PowerNet from SSBM Used to control and monitor UPMs SSBM. Used to control and monitor UPMs.
  • Page 179 Terminate each redundant PowerNet network at the end modules in the system. Refer to drawing 164201373---4, sheet 2 for typical termination points. Refer to applicable chapters for information about installing control wiring. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402...
  • Page 180 Powerware 9315 750 CAN A and CAN B Interface Location A ---24 CUSTOMER INTERFACE CAN B CAN A DESCRIPTION: UPM CAN INTERFACE: POWERWARE 9315-- 625/750 UPMs DRAWING NO: 164201373---6 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM SHEET: 2 of 3 164201373 Rev.
  • Page 181 CONTROL POWER --- 12VDC J2---1 CAN B A1TB7-4 CONTROL POWER --- GND J2---2 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 Name Channel A connection of PowerNet from SSBM. Used to control and monitor UPMs. SSBM. Used to control and monitor UPMs.
  • Page 182 A ---26 Table N. Remote EPO REMOTE SWITCH TWISTED WIRES (2) tied into any other circuits. DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM REMOTE EMERGENCY POWER OFF SHEET: 164201373---7 164201373 Rev. A 1 of 2 092402...
  • Page 183 115.8 (4.56) 114.3 (4.50) TO SSBM Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 TO OTHER Dimensions are in millimeters (inches) EQUIPMENT DESCRIPTION: DRAWING NO: 11.9 (0.47) 88.9 (3.50) SQUARE Knockout pattern typ. 5 sides REMOTE EMERGENCY POWER OFF...
  • Page 184 Dimensions are in millimeters (inches) A ---28 197.47 (7.75) 88.9 (3.50) DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 285.7 (11.25) MAX. WIRE SIZE: NO. 14 AWG MIN. WIRE SIZE: NO. 18 AWG 216.58 (8.50) SURFACE MOUNT...
  • Page 185 (1.12) 41.1 (1.62) 190.5 88.9 (7.50) (3.50) EXISTING INTERNAL WIRING Dimensions are in millimeters (inches) Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 215.9 (8.5) 196.8 (7.75) 19.0 Relay Interface Module CONDUIT AND WIRING SUPPLIED BY CUSTOMER.
  • Page 186 15---PIN D ---SUB CONNECTORS 74.6 (2.94) 171.5 (6.75) KNOCKOUTS PROVIDED ON FIVE SURFACES DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 285.7 (11.25) 273.1 (10.75) RELAY INTERFACE MODULE SHEET: 164201373---9 164201373 Rev. A 2 of 2 092402...
  • Page 187 (7.50) CONDUIT AND WIRING SUPPLIED BY CUSTOMER. MAX. DISTANCE BETWEEN REMOTE MONITOR AND SBM NOT TO EXCEED 500 FEET. Dimensions are in millimeters (inches) Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 197.47 (7.75) 88.9 (3.50)
  • Page 188 DESCRIPTION: PowerHandlerPlus SSBM DRAWING NO: SHEET: 164201373---11 1 of 4 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM A ---32 164201373 Rev. A 092402...
  • Page 189 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 DESCRIPTION: PowerHandlerPlus SSBM DRAWING NO: 164201373---11 SHEET: 2 of 4 A ---33...
  • Page 190 A ---34 For 3 Phase, 4 wire SSBM option ONLY: Neutral Bus in Sections 2 and 3. DESCRIPTION: DRAWING NO: Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM PowerHandlerPlus SSBM SHEET: 164201373---11 164201373 Rev. A 3 of 4 092402...
  • Page 191 Floor Mounting Details (NOTE: Frame and bottom main bus shown only for clarity.) Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 DESCRIPTION: PowerHandlerPlus SSBM DRAWING NO: 164201373---11 SHEET: 4 of 4 A ---35...
  • Page 192 DESCRIPTION: PowerHandlerPlus SSBM with SMB DRAWING NO: SHEET: 164201373---12 1 of 4 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM A ---36 164201373 Rev. A 092402...
  • Page 193 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 DESCRIPTION: PowerHandlerPlus SSBM with SMB DRAWING NO: 164201373---12 SHEET: 2 of 4 A ---37...
  • Page 194 DESCRIPTION: PowerHandlerPlus SSBM with SMB DRAWING NO: SHEET: 164201373---12 3 of 4 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM A ---38 164201373 Rev. A 092402...
  • Page 195 Floor Mounting Details (NOTE: Frame and bottom main bus shown only for clarity.) Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 DESCRIPTION: PowerHandlerPlus SSBM with SMB DRAWING NO: 164201373---12 SHEET: 4 of 4 A ---39...
  • Page 196 CONTROL/MONITOR PANEL FRONT VIEW DESCRIPTION: TYPICAL SSBM CONTROL SECTION DRAWING NO: SHEET: 164201373---13 1 of 4 110915520 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM A ---40 164201373 Rev. A 092402...
  • Page 197 WILL BE ONE OF THE FOLLOWING: SMB ELECTRICAL INTERLOCK (A10) SMB ELECTRICAL INTERLOCK WITH REDUNDANT CBP (A11) 110915520 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 NETWORK POWER SUPPLY PANEL (A13) FRONT VIEW FRONT DOORS REMOVED...
  • Page 198 POWERNODE PANEL 110915520 A ---42 CUSTOMER INTERFACE PANEL (OPTIONAL) DESCRIPTION: TYPICAL SSBM CONTROL SECTION DRAWING NO: 164201373---13 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM SHEET: 3 of 4 164201373 Rev. A 092402...
  • Page 199 SMB ELECTRICAL INTERLOCK PANEL (A10) (OPTIONAL) SMB ELECTRICAL INTERLOCK PANEL (A11) WITH REDUNDANT CBP CONTROLS (OPTIONAL) 110915520 Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM 164201373 Rev. A 092402 DESCRIPTION: TYPICAL SSBM CONTROL SECTION DRAWING NO: 164201373---13 SHEET: 4 of 4...
  • Page 200 750 --- 750/675 750 --- 750/675 NOTES: 1. * = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements between the UPS and its output transformer. A ---44 UPM Output-to-SSBM Cable Configuration Minimum Conductor Size, 3∅, (1) Neutral, (1) Gnd...
  • Page 201 UPMs connected to any SSBM shall not exceed eight. 2. Maximum conductor size considered: 700 kcmil. 3. * = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements between the UPS and its output transformer.
  • Page 202 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM A ---46 164201373 Rev. A 092402...
  • Page 203 If, in the opinion of Powerware, the Unit fails to meet published specifications and the defect is within the terms of this warranty, the Unit will be repaired or replaced at the option of Powerware with no charge for replacement parts. Labor required, to make the repairs or replacement installation, and travel costs incurred by Powerware’s representatives, is not included under the...
  • Page 204 This Page Intentionally Left Blank. Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM W--2 164201373 Rev. A 092402...
  • Page 205    5HY $...

Table of Contents