Powerware 9305 HS Series User And Installation Manual

20 - 80 kva parallel ups systems

Advertisement

User's and Installation Manual
20 - 80 kVA parallel UPS systems

Advertisement

Table of Contents
loading

Summary of Contents for Powerware 9305 HS Series

  • Page 1 User’s and Installation Manual 20 - 80 kVA parallel UPS systems...
  • Page 3: Table Of Contents

    User’s and Installation Manual 20 - 80 kVA Parallel Systems 1018390 Revision C Table of content: 1. Safety Instructions ........................5 1.1 General ..........................5 1.2 Installation and service ......................5 1.3 User operations ........................6 2. Introduction ..........................7 2.1 Overview ..........................
  • Page 4 Copyright 2003 The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission.
  • Page 5: Safety Instructions

    1. Safety Instructions 1.1 General Warning! The complete safety instructions (p/n: 1009917) must be followed when installing, operating and servicing the parallel UPS system. Study the complete safety instructions carefully. Because of the high energy stored within the batteries, the UPS equipment must be handled with care.
  • Page 6: User Operations

    1.3 User operations Warning! Do not open the UPS cabinet! Some components inside the UPS cabinet carry high voltages. To touch them may prove fatal or cause injury. All operations inside the unit must be carried out only by service personnel from the manufacturer or from an agent authorised by the manufacturer.
  • Page 7: Introduction

    2. Introduction 2.1 Overview This manual gives you the necessary information about parallel UPS systems in redundancy or capacity configuration. The largest systems include maximum of four UPS modules in parallel configuration. Instructions and procedures are covered in this manual: shipping; storing; handling; installation; user start-up and operation;...
  • Page 8: System Description

    3. System Description 3.1 Overview Parallel UPS configurations are recognised as either redundancy or capacity systems. The redundancy system is used to improve the system reliability with N+1 redundant UPS module. The capacity system for its part provides the maximum output power without focusing to the highest system reliability.
  • Page 9: Theory Of Operation

    3.2 Theory of operation A double conversion on-line UPS conditions the raw mains and supplies continuous, clean three-phase power to the critical systems. It keeps the battery constantly charged while feeding the critical load. The UPS will continue to supply clean power without any interruption at the output even at mains failure.
  • Page 10: Sizing

    The mains is rectified and boosted to DC power in the rectifier part. The rectifier provides power to the battery charger and the inverter load. The battery charger keeps the battery in recharged condition with ABM™ technology. The DC Link connects the rectifier output with the inverter input.
  • Page 11: Instructions And Preventive Maintenance

    4. Instructions and preventive maintenance 4.1 General Proper provision must be made for transportation and handling because of heavy weight and high energy stored within batteries. See technical specifications for dimensions and weights of the UPS modules. 4.2 Unpacking and incoming inspection Unpack the equipment and remove the shipping and packing materials.
  • Page 12: Storage

    4.3 Storage UPS modules must be stored in the original packing and shipping pallet. They should be handled with care. Make sure that you do not stack the pallets when the equipment is placed to local warehouse for storage. If the UPS is not immediately installed the following must be remembered: •...
  • Page 13: Maintenance

    4.7 Maintenance Warning! Maintenance work must be performed only by a service person with the service training completed. One should sign a service and maintenance contract with an authorised local service centre. The maintenance work for parallel UPS system can be done with the system bypass switch. The good condition of the batteries is crucial to correct operation of the parallel UPS system.
  • Page 14: Mechanical Installation

    5. Mechanical installation 5.1 Overview Environmental requirements and restrictions described in the technical specification shall be met to guarantee the proper function and safety of the equipment. Figure 5. Dimensions of the parallel UPS system components. 20 - 80 kVA parallel UPS system 1018390 User’s and Installation Manual Revision C...
  • Page 15: Placing Ups Modules

    The installation surface must be smooth and steady to carry the point and distributed loading of the whole parallel UPS system. ) . s ) . s Table 1. The floor loading of the parallel UPS system components. 5.2 Placing UPS modules Maintain 1000-mm clearance at front of the UPS modules for service, user operations, and fire escape safety.
  • Page 16 Figure 6b. Ventilation and space requirements for 40 - 80 kVA UPS. Power cables shall be routed from the bottom or rear side of the UPS modules. The cables shall be protected with a casing tube. The size and location of the cable entries is shown in the drawing. Figure 7.
  • Page 17: Placing Battery Cabinets

    5.3 Placing battery cabinets The detailed installation instructions for the external battery cabinets are included in the shipment. External battery cabinets shall be installed next to the UPS modules and the location of the cable routing is under the external battery cabinets: •...
  • Page 18: Electrical Installation

    6. Electrical installation 6.1 Overview Qualified personnel should do the electrical installation planning of the parallel UPS system in compliance with the warnings laid down in this manual. The inspection and initial start up of the UPS modules and external battery cabinets must be carried out by service engineer from the manufacturer or from an agent authorised by the manufacturer.
  • Page 19: Input And Output Power Cables

    6.3 Input and output power cables Input terminals X1 and X2 have a five-wire connection (L1, L2, L3, N, and PE) for the rectifier and bypass line. The output terminal X3 is located directly in the circuit breaker. Cables with copper conductors should be used to fit the terminals. Figure 10.
  • Page 20: Parallel Operation

    6.4 Parallel operation UPS modules have a cable connection between them to inform about the phase synchronism of the bypass voltages. It is needed in order to transfer the critical load back from the bypass line to inverters at the same time. The transfer from inverters to bypass functions without the data bus connection in case of overload situation.
  • Page 21 Figure 12. Wiring diagram of the external battery cabinets D and E. Figure 13. Wiring diagram of the external battery cabinet F . 1018390 20 - 80 kVA parallel UPS systems Revision C User’s and Installation Manual...
  • Page 22 Battery configurations with 40-80 kVA UPS modules Power cables should be connected to the battery terminals of the UPS modules. See the battery wiring diagrams and chapter ‘Location of terminals’ for the correct power cable connections. Figure 14. Wiring diagram of the external battery cabinets D and E. 20 - 80 kVA parallel UPS system 1018390 User’s and Installation Manual...
  • Page 23: Spm Tie Cabinet Options

    Figure 15. Wiring diagram of the external battery cabinets F . 6.6 SPM tie cabinet options The system parallel module (SPM) has input connections up to four or two parallel UPS modules and make-before-brake type of system bypass switch. The UPS manufacturer provides five (5) different types of System Parallel Modules: t s - t s -...
  • Page 24 Figure 16. A parallel 4 x UPS configuration with the SPM tie cabinet Local regulations and installation environment shall be considered when selecting power cables and fuses/breakers. The recommendations of this manual can be used as a guideline for the electrical wiring and installation. Slow gG fuses or C-type breakers should be used for short-circuit protection of the power cables.
  • Page 25 Figure 17. Cable routing of SPM9305/9340-130-2 and SPM9305-80-4 tie cabinets. Figure 18. Cable routing of SPM9305-60-4 tie cabinets. 1018390 20 - 80 kVA parallel UPS systems Revision C User’s and Installation Manual...
  • Page 26 Figure 19. Wiring diagram with SPM9305/9340-130-2 tie cabinet. 20 - 80 kVA parallel UPS system 1018390 User’s and Installation Manual Revision C...
  • Page 27 Figure 20. Wiring diagram with SPM9305-60-4 and SPM9305-80-4 tie cabinets. 1018390 20 - 80 kVA parallel UPS systems Revision C User’s and Installation Manual...
  • Page 28 ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ² ²...
  • Page 29 Figure 21 . Cable routing and mounting holes for SPM9305-60-2 and SPM9305-30-2 tie cabinets. 1018390 20 - 80 kVA parallel UPS systems Revision C User’s and Installation Manual...
  • Page 30 Figure 22. Location of SPM9305-60-2 and SPM9305-30-2 control switches. 20 - 80 kVA parallel UPS system 1018390 User’s and Installation Manual Revision C...
  • Page 31 Figure 23. Wiring diagram with SPM9305-30-2 tie cabinet. ² ² ² ² Table 5. Recommended cables and fuses for the wiring diagram. 1018390 20 - 80 kVA parallel UPS systems Revision C User’s and Installation Manual...
  • Page 32 Figure 24. Wiring diagram with SPM9305-60-2 tie cabinet. ² ² ² ² Table 6. Recommended cables and fuses for the wiring diagram. 20 - 80 kVA parallel UPS system 1018390 User’s and Installation Manual Revision C...
  • Page 33: Input Filter Option

    Local tie panel solutions The internal wiring diagrams of SPM9305 tie cabinets can be used as a reference when designing local tie panels. Parallel UPS configurations require a tie panel at the system output. It must facilitate service switches for each UPS module output. The system bypass switch is optional but helps when doing the maintenance for the whole parallel UPS system.
  • Page 34: Installation Check List

    6.8 Installation check list Check that electrical connections to the installation site have been properly executed. Check that input cables from a low-voltage switchgear are connected to the UPS modules and the system parallel panel. Make sure that the neutral of UPS input is properly connected.
  • Page 35: Software

    Figure 25. Location of terminals in 20/30 kVA (left) and 40/50/60 kVA (right) UPS modules. Cable holders should be used for routing to the terminals. Note! All communication connections must not have a galvanic connection to any mains connected circuits. Reinforced insulation to the mains is required for equipment and cables connected to these connections.
  • Page 36: Potential Free Relay Outputs

    The RS-232 interface on terminal X101 uses a 9-pin male D-sub connector. It is used for connecting a modem (or a computer) to the UPS module. The data includes information about the utility, load and the status of the UPS module. r e i t t i r e t...
  • Page 37: Signal Inputs

    7.5 Signal inputs The programmable auxiliary inputs are used to control the operation of UPS modules. A double shielded cable is the best alternative but single shielded twisted multipair cable is also usable. Remember that signals should not have a galvanic connection to any mains connected circuits.
  • Page 38: Start-Up And Operation

    8. Start-up and operation 8.1 Overview This chapter contains the necessary information on how to use the UPS system. The starting up and shutting down procedures described here are only used on a few occasions for example when preparing for a long term mains failure or changing the batteries. In normal operation the UPS system runs automatically.
  • Page 39: Operating System Bypass Switch

    Check that the optional system bypass switch is in the ‘BYPASS’ position, and the individual service switches are in the ON position. If the system configuration does not include the external system bypass switch, the critical load must be disconnected, (when cold battery start) or UPS modules must be started immediately after each one (during 30 seconds) to prevent overload situation at the system start-up.
  • Page 40: Shut-Down Procedure

    Check that the unsynchronised alarm is not active in the UPS modules. (Press Menu button, choose UPS status display) Turn the maintenance bypass switch to BYPASS position. Warning! The use of the maintenance bypass switch will cause a break in the output voltage if the input voltage or frequency is not correct and the UPS system is not synchronised to mains.
  • Page 41: Control Panel Operation

    It is possible to shut down a single UPS module and still get maximum protection for the critical load. This operation requires that the parallel system to be in the N+1 redundancy mode. In capacity mode, the system bypass switch should be used to transfer the system to bypass power.
  • Page 42: Control Panel Displays

    This green LED is lit when there is voltage at the output terminals and when the UPS is in normal or static bypass mode. This yellow LED is lit when the UPS is operating in battery mode. When this LED is blinking the battery voltage is low and only few minutes of backup time is left.
  • Page 43 Figure 30. Menu map UPS Status display UPS Status display will indicate the current operation mode of the UPS on the top row of the display. The display will automatically come to this display state if there is some abnormal operation in the unit.
  • Page 44 Meters display The Meters display will inform various measurements of the UPS. Different measurements can be selected with ↓ ↓ ↓ ↓ ↓ and ↑ ↑ ↑ ↑ ↑ buttons. Following measurement information is available: • Output voltage, shows AC voltage of each output phase •...
  • Page 45: Troubleshooting

    Display Data display The display shows information about the display software: revision, compilation date and check sum. To adjust the contrast or select a different language push ↵ ↵ ↵ ↵ ↵ button down during three seconds. These options can be scrolled with ↓ ↓ ↓ ↓ ↓ and ↓ ↓ ↓ ↓ ↓ buttons. Pressing Menu button will return the display to Menu display.
  • Page 46: Warranty

    r a l a t l s s i e t t e t t s t r . t i . e t a t l . t i a t l . t i . y r a i t e f i l l a a t l...
  • Page 47: Technical Specifications

    11. Technical specifications 1. General 1.1 Rated power 20 kVA, 30 kVA, 40 kVA, 50 kVA, 60 kVA, 80 kVA; at p.f. 0,7, inductive or non linear load 1.2 Technology Double conversion online topology with automatic bypass switch and maintenance bypass switch. Voltage and Frequency Independent operation: Class VFI-SS-111 by IEC 62040-3 2.
  • Page 48 Single UPS modules i c i a t l x 2 x The number indicated in parentheses are for units with battery banks of 32 pcs battery system. Parallel Hot Sync™ systems 4. Environmental 4.1 Ambient temperature 0° ... + 40°C operating +15°C ...
  • Page 49 4.7 Cooling air requirements Q=300 x P/t, where: Q=air flow in m3/h, P=power losses in kW, t=temp. rise in celcius, which means that each kW of losses needs an airflow of 300 m3/hour trough a room to keep temp raise at 10 celcius max.
  • Page 50 Appendix A – Dimension drawings 20-30 kVA UPS 20 - 80 kVA parallel UPS system 1018390 User’s and Installation Manual Revision C...
  • Page 51 Appendix B – Dimension drawings 40 - 80 kVA UPS 1018390 20 - 80 kVA parallel UPS systems Revision C User’s and Installation Manual...
  • Page 52 Appendix C – Dimension drawings SPM9305 Ref. SPM9305-80-4 / SPM9305-60-4 / SPM9305/9340-130-2 20 - 80 kVA parallel UPS system 1018390 User’s and Installation Manual Revision C...

Table of Contents