Location - President Fs; Wall & Floor Fixing; Venting Configurations - Valor 530SAN Installation And Owner's Manual

Direct vent gas fireplace heater with logs or coals
Table of Contents

Advertisement

4.1. Wall & Floor Fixing
The President FS can be installed against a wall or in the
room away from walls. The appliance is designed to be fixed
to the floor. The appliance can additionally or alternatively be
fixed to a rear wall. The fixing positions are shown in figure
4.
If the appliance is installed directly on carpeting, tile or other
combustible material other than wood flooring, it must be
installed on a metal or wood panel extending the full width
and depth of the appliance.

4.2. Venting configurations

4.2.1. Flat on wall
Requires Valor vent kit #551DVK or Dura-vent pipe length
with adapter #817VAK and Dura-vent terminal cap.
The location requirements are shown in figure 5.
The horizontal vent run can not be extended beyond the
dimensions shown in figure 5 by the use of any vent accessory
pipes.
4.2.2. Flat on wall with snorkel termination (Fig.6)
For use on horizontal vent installations where the outside
ground level is too close to the standard terminal. Adapter
#817VAK, a Dura-vent pipe length and snorkel termination
#981 or #982 will be required (See vent options section of this
manual).
4. LOCATION – PRESIDENT FS
Figure 4 President FS fixing holes
Figure 5
Figure 6
7