Baxi Solo 3 PFL 30 Installation & Servicing Instructions Manual page 13

Wall mounted powered flue gas fired central heating units
Table of Contents

Advertisement

Maximum Length = 2m inc. 2 x 45° bends
Vertical
Flues
(Twin Pipe)
Maximum Length = 21m
inc. 4 x 45° bends
Vertical
Flues
Maximum Length = 2m
inc. 2 x 90° bends
© Baxi Heating UK Ltd 2009
Horizontal
Flues
4.0 Site Requirement
4.8
Flue Options
1. The Baxi Solo 3 PFL can be fitted with flue systems
as illustrated.
2, The standard flue is suitable only for horizontal
applications.
3. Maximum permissible equivalent flue lengths are:-
Horizontal
3.0 metres
Vertical
Vertical (Twin)
4. Any additional "in line" bends in the flue system
must be taken into consideration. Their equivalent
lengths are:-
Concentric Pipes:
45° bend
90° bend
Twin Flue Pipes
Air Duct
45° bend
1.3 metres
90° bend
4.8 metres
5. The illustrations opposite show examples of
maximum equivalent lengths.
6. Instructions for guidance and fitting are included in
each kit.
IMPORTANT: All flue systems must be securely
supported at least once every metre. Suitable pipe
supports are available as accessories.
4.0 metres
20.0 metres
0.5 metres
1.0 metres
Flue Duct
3.3 metres
12.0 metres
13